5-5-3 DAR/PI measurement procedure
The DAR and PI are measured automatically by the continual insulation
resistance measurement. The DAR value is displayed in 1 minute after
the start of measurement and the PI value in 10 minutes after.
Since the DAR and PI values are obtained by arithmetic operations,
“no” is displayed when the calculation is impossible because the
measurement is “0.0 MΩ” or “OL”.
Example of display during DAR/PI measurement
The display in the area inside the frame varies as follows.
“- - - ” is displayed for 1 minute after the start of measurement.
The DAR value is displayed in 1 minute.
The PI value is displayed in 10 minutes.
After 10 minutes, the DAR and PI values can be checked
alternately by pressing the DISPLAY button.
Example of display after completion of measurement
(A)
Timer
(B)
Measured Value
and Terminal voltage
(C)
DAR/PI value
After completion of measurement, each press of the DISPLAY
button can switch the four values, including the one at the
completion of measurement, one at 15 or 30 seconds, one at 1
minute and one at 10 minutes after the start of measurement.