17.2. TCP/IP BACNET
PRO-REG controller is equipped with an integrated RJ45 port
for TCP/IP communication, as support for BACnet IP commu-
nication. It’s necessary to confi gure the IP address on each
controller, and activate and address the BACnet IP using
ETOOL software (E tool© is delivered as a self-installing pro-
gram and can be downloaded from
http://www.regincontrols.com/Root/Documentations/
42_105786/CorrigoEVentilation%203.4-1-24.zip)
It is necessary to indicate the names, IP fi xed directions, sub-
net masks and default gateway of each unit connected to the same network.
18. REPLACEMENT OF THE BATTERY FROM THE CORRIGO PROGRAMMABLE
LOGIC
CONTROLLER
When the “battery low” alarm appears and the red indicator light is lit, it means that the
backup battery to save the memory and the real time clock is too low.
The procedure to change the battery is described below.
A capacitor allows backing up the memory and running the clock for approximately 10
minutes after the power is switched off.
TCP/IP
45
U
I4
44
U
I3
43
A
g
n
d
42
U
I2
41
U
I1
40
A
g
n
d
35
A
I4
34
A
I3
33
A
g
n
d
Содержание UTBS PRO-REG Series
Страница 1: ...SERIE UTBS PRO REG EN...
Страница 2: ......
Страница 29: ...29 10 CONTROL DIAGRAM Version with electric batteries...
Страница 30: ...30 Versions with hot and or cold water coils...
Страница 31: ...31 Versions with reversible water coil...
Страница 62: ...62 22 WIRING DIAGRAMS...
Страница 63: ...63...
Страница 64: ...64...
Страница 65: ...65...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68...
Страница 69: ...69...
Страница 70: ...70...
Страница 71: ...71...