11.4. POSTHEATER CONTROL
It is possible selecting between 4 different types of postheating control.
To select it follow the following sequence:
11.4.1. Constant supply air temperature maintenance
Constant supply air
T°C
Heating mode
Temperature controller works comparing supply air
temperature with set point defi ned by console.
11.4.2. Constant ambient temperature maintenance
Room T°C control
Heating mode
Supply air temperature is controlled in cascade way
with ambient temperature. Supply air temperature
is defi ned depending on difference between ambient
temperature and set point. In front of request, the
controller tries to keep ambient temperature limi-
ting duct temperature, which is maintained around
12 and 30ºC, at same time.