57
The following table shows the mode to proceed to detect and resolve any incidents shown:
Alarm
number
Alarm text
Description
Tipo
alarma
1
Run Error Supply Air Fan
Malfunction of supply air fan
A
6
Change Filter
Prefi lter % Filter need replacement
C
10
Fire Alarm
Fire alarm activated
C
11
Remote off active
Remote On/Off active
A
23
Electric heating is overheated
Electric Heater Thermal protectors activated
C
24
Frost risk
Frost protection function is overriding the control
of the water heater output
C
25
Water temp too low, system off
Water temperature below frost limit value (<7ºC)
A
27
Sensor error outdoor temp
Malfunction of outdoor air temperature sensor
C
41
Manual heater control
The electric heater is in manual mode
C
42
Manual exchanger control
Heat exchanger output in manual control
C
43
Manual cooler control
Cooling output is in manual control
A
48
Internal battery error
Internal battery needs replacing
A
49
Sensor error Supply Air temp
Malfunction of supply air temperature sensor
A
50
Sensor error Extract Air temp
Malfunction of extraction air temperature sensor
A
55
Sensor error SAF pressure
Malfunction of supply air pressure sensor
A
58
Sensor error Frost Protection temp
Malfunction of water temperature sensor
C
90
Change External Filter
Extraction Air Filter needs replacement
(&
.
;C;H=;D9OEF;H7J?EDI
• If any problems are noted on the unit, turn it off using the emergency shut-off device.
• These emergency operations will generally be the result of some problem with the elec-
trical circuit, in which case you may have problems with the motors. You will therefore
need to disconnect the power to locate the fault, which may be inside the unit (short
circuit) or external to it (problems with the power supply, voltage variations, etc.).
• In the event of fire, it must be extinguished using suitable extinguishers. Extinguishers
should be appropriate for use on electrical fires.
('
.
FH;L;DJ?L;C7?DJ;D7D9;
• Preventive maintenance is a preset programme of checks that is followed regularly to
prevent equipment breakdowns.
• The supplemental Building Facility Technical Regulations are applicable at all times to
maintenance standards, except when justified otherwise for technical reasons.
• The maintenance supervisor should keep a copy of the preventive maintenance recom-
mendations given below on file, making as many copies as needed for use.
• According to the equipment’s operating needs, it is crucial to make a list of those ele-
ments that are needed to quickly resolve equipment faults. This list will serve to deter-
mine the spare parts inventory needed to be able to perform repairs quickly.
Содержание UTBS PRO-REG Series
Страница 1: ...SERIE UTBS PRO REG EN...
Страница 2: ......
Страница 29: ...29 10 CONTROL DIAGRAM Version with electric batteries...
Страница 30: ...30 Versions with hot and or cold water coils...
Страница 31: ...31 Versions with reversible water coil...
Страница 62: ...62 22 WIRING DIAGRAMS...
Страница 63: ...63...
Страница 64: ...64...
Страница 65: ...65...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68...
Страница 69: ...69...
Страница 70: ...70...
Страница 71: ...71...