5-78
10-18
Loop Speed
Factory setting
1.00
Settings
0.00~400.00
Hz
10-19
Loop Point
Factory setting
10
Settings
0~20000
10-20
Division (scaling) factor for PG04/05
Factory setting
1
Settings
1~128
1
Parameter 10-20 is used when the drive must follow a second encoder for speed reference.
The main encoder (A) is a factor of the second encoder (B) as follows.
If Pr.10-20 is set to 1, then the feedback from both encoders are 1:1, (1 pulse on encoder A
= one pulse on encoder B). If encoder A is 1 pulse for every 100 pulses on encoder B,
then Pr. 10-20 should be set at 100.
1
Drawing for position control.
The origin(z phase)
10-16
Orient Speed
10-17
Creep point
10-09
PG Location Control Point
10-19
Loop Point
10-18
Loop Speed
1
Position control timing:
Master speed
Speed 0
Fwd/Rev
Location control
Location achieve
(Multi-function input)
(Multi-function output
02-01~02-06 set 30
02-11~02-14 set 31
Speed of 10-16
10-17 Creep point
speed of 10-18
10-19
Loop Point
10-09
PG Location
Control Point
10-21
Feed Forward
Factory setting 5.0
Settings
0.0~100.0%
10-22
Position Control Speed Gain
Factory setting 90.0
Settings
0.0~100.0%
Содержание S3000 Series
Страница 1: ...440V Series Multifunctional VectorControl ACMotor Drivers User Manual S3000 Series AC Motor Drivers...
Страница 8: ...2 5 DIMENTIONS 2 5...
Страница 9: ...2 6 403 216...
Страница 10: ...2 7...
Страница 11: ...2 8 S3000 IP06...