5-29
03-09
Analog Input 1 Gain (AVI)
Factory setting
100.0
Settings
-500.0~+500.0%
03-10
Analog Input 2 Gain (ACI)
Factory setting
125.0
Settings
-500.0~+500.0%
03-11
Analog Input 3 Gain (AUI)
Factory setting
100.0
Settings
-500.0~+500.0%
1
Pr.03-09 to 03-11 are used to adjust the 10V or 20mA corresponding frequency value.
Example:
If Pr.03-00 = 10, Pr.01-00 =60, and you would like the 10V position of AVI (0-10V ) to
equal 60Hz, than use the following equation to program the Gain.
Pr.03-09 = ( 1+ (Pr.03-00/Pr.01-00))x 100
03-12
Addition Function of the Analog Inputs
Factory setting
0
Settings
0 disable addition function (AVI, ACI, AUI)
1 enable addition function
1
If the addition between AVI, ACI and AUI are disabled, and that the selections on the
analog input setting function are similar among the three, the priority order of the analog
input will be: AVI > ACI > AUI.
Example 1:
60Hz
0V
10V
03-03=0V
03-06=d0
03-09=100%
Example 2:
60Hz
1V
10V
03-03=1V
03-06=d1
03-09=10/8=125%
9V