4-28
Group 9: Communication Parameter
Parameters
Functions
Settings
Factory
Setting
Customer
09-00
Communication
Address
1~254
1
09-01
Transmission Speed of
the Communication
4.8 ~ 115.2 Kbits/s
9.6
09-02
Transmission Fault
Treatment
0: warn and keep operating
1: warn and RAMP to stop
2: warn and COAST to stop
3: no treatment and no display
3
09-03
Overtime
Detection
0: disabled
1~100 s
0
09-04
Communication
Protocol
0: 7, N, 1 for ASCII
1: 7, N, 2 for ASCII
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII
7: 8, N, 2 for ASCII
8: 8, E, 1 for ASCII
9: 8, O, 1 for ASCII
10: 8, E, 2 for ASCII
11: 8, O, 2 for ASCII
12: 8, N, 1 for RTU
13: 8, N, 2 for RTU
14: 8, E, 1 for RTU
15: 8, O, 1 for RTU
16: 8, E, 2 for RTU
17: 8, O, 2 for RTU
0
09-05
Keypad Transmission
Fault Treatment
0: warn and keep operating
1: warn and RAMP to stop
2: warn and COAST to stop
0