Chapter 9 Test after installation
Go through the check list below after the installing the equipment.
Check list
OK
1
Turn the BNWAS on, set the timer on 3 minutes and the bridge watch mode in manual.
2
Go to the external reset unit(BNW-52, motion sensor), then do not move for 3 minutes.
After 3 minutes, check if Reset unit (BNW-52) has lighted up then check if lighting stops
when you move near to the motion sensor or press the reset button.
3
Do not move for 3 minutes. See if reset unit lights up, then check if reset unit (BNW-52)
activates the 1
st
stage audible alarm after 15 seconds from then.
4
Go to the captain/master and/or the back-up officer’s cabin to check if the BNW-53
activates the 2
nd
stage audible alarm after 15 seconds from the 1
st
stage audible alarm.
5
Go to the crew’s office and check if the 3
rd
stage audible alarm activates after 90~180
seconds (adjustable) from the 2
nd
stage audible alarm.
6
Go to the bridge and reset all the alarms by pressing the reset button.
7
Press the emergency call button for 2 seconds. Check if the 3
rd
stage alarm is displayed
after the 2
nd
stage alarm. Turn the alarm off by pressing the emergency call button for 2
seconds..
8
Disconnect the main power. Check if you see the Main Power Failure on the display.
Connect the main power again.
9
Disconnect the backup power. Check if you see the Back Up Power Failure on the display..
10
If failure relay output is used, check if the equipment connected to the failure relay works
properly. Then connect the backup power
11
If pulse reset unit is used, then connect the equipment to the RES3/PULS terminal. Check if
the other equipment can reset the timer.
12
If VDR (black box) is used, check if the VDR receives data information from the Processor
unit (BNW-51).
13
If vessel’s heading or the track control system is connected, set the BNWAS’ alarm mode
as AUTO. Check if the timer works and ACTIVE appears under ALARM STATE when the
vessel’s heading or track control system is operating.