2nd Edition of TEMP2000_Series IM : July. 16. 2010 Page 31 / 87
▶
This screen shows floating point selection.
Table 3-1 Sensor Input Setup Screen-1 Parameter
Parameter
Range
Unit
Default
Sensor Group
T/C, RTD, DCV
ABS
T/C
TC-K1, TC-K2, TC-J, TC-E,
TC-T, TC-R, TC-B, TC-S, TC-L,
TC-N, TC-U, TC-W, TC-PLA,
TC-C
ABS
TC-K2
(When Sensor Group is T/C)
PT A, PT B, PT C, PT D,
JPT A, JPT B
ABS
PT A
(When Sensor Group is RTD)
Sensor Type
0.4~2.0V, 1~5V, 0~10V,
-1~20MV, 0~100MV
ABS
0.4~2.0V
(When Sensor Group is DCV)
℃, ℉
ABS
℃
Display Unit
℃, ℉, SPACE, %, Pa, kPa, %RH, mV,
V, Ω, mmHg, Kgf
ABS
℃
(When Sensor Group is DCV)
Floating Point Position
0 ~ 3
ABS
1
(When Sensor Group is DCV)
Thermocouple
Indication
T/C, TC+RJC, RJC
ABS
TC+RJC
(When Sensor Group is T/C)
Range High
EU
EU(100.0%)
Rang Low
EU(0.0 ~ 100.0%)
Range Low < Range High
EU
EU(0.0%)
Input Compensation
EUS (-100.0 ~ 100.0%)
EUS
EUS(0.0%)
Sensor Filter
0 ~ 120 SEC
SEC
0
SCALE Hight Limit
℃
100.0
(When Sensor Group is DCV)
SCALE Low Limit
-199.9 ~ 3000.0℃
SCALE Low Limit < SCALE Hight Limit
℃
0.0
(When Sensor Group is DCV)
* Can not change Sensor Group, Sensor Type, Range High, Range Low, Display Unit, Scale Hight/Low Limit.
[Figure 3-9] Floating Point Setup (DCV)