2nd Edition of TEMP2000_Series IM : July. 16. 2010 Page 11 / 87
1.3 Wiring
Precaution
▶
Switch off the main power supply and make sure that no current flows in all the circuits before
the wiring work.
▶
Do not touch the real terminal part while the power is on.
▶
Main circuit breaker must be kept in OFF state until all the wiring work is done.
1.3.1 Wiring Specifications
1.3.1.1 Power cable specification
▶
Vinyl-insulated shielding cable KSC 3304 0.9 ~ 2.0 ㎟
1.3.1.2 Terminal connector specification
▶
Use crimping terminal with insulating sleeve proper for M3 screw as shown in the figure.
1.3.1.3 Countermeasures against noise
▶
Noise source
(A)
Relay and Electrical contacts
(B)
SOLENOID COIL, SOLENOID VALVE
(C)
Power Line
(D)
Inductive Load
(E)
INVERTOR
(F)
Rectifier of a Motor
(G)
Phase-angle controlled SCR
(H)
Wireless communication devices
(I)
Welding machines
(J)
High-tension magneto-Ignition system
▶
Countermeasures against noise
Notice following guide while wiring work.
(A)
The wires of input signal should be apart from power line and grounding line.
(B)
Use a shielded wire to guard against a noise from electrostatic induction. Multi-point grounding
should be avoided and connect the shield wire to ground terminal if necessary.
(C)
It is effective to make the input wires as a twisted pair to prevent an electromagnetic noise.
(D)
When using an auxiliary relay, refer to section 2-1-4-5.