2nd Edition of TEMP2000_Series IM : July. 16. 2010 Page 58 / 87
8. ON/OFF 시그널
▶
This screen can set the range of ON/OFF Signal, High & Low Limit Deviation.
▶
6 ON / OFF signals can be set.
▶
[5.1.3 Relay Setup Screen-3] can set Relay Number and Delay Time.
8.1 ON/OFF Signal Setting
①
Set CH1 Low Limit SP for ON/OFF Signal Operation.
②
Set CH1 Middle SP for ON/OFF Signal Operation.
③
Set CH1 High Limit SP for ON/OFF Signal Operation.
④
Set Operating Point at High Limit Section.
⑤
Set Operating Point at Low Limit Section.
Table 8-1 CH1 ON/OFF Signal Setup Parameter
Parameter
Range
Unit
Default
T#n LOW SP
EU
EU(0.0%)
T#n MIDDLE SP
EU
EU(0.0%)
T#n HIGH SP
EU(0.0~100.0%)
Range Low ≤ T#n LOW SP
<T#n MIDDLE SP < T#n HIGH SP ≤ Range High
EU
EU(0.0%)
T#n HIGH 편차
EUS(0.0~10.0%)
EUS
EUS(0.0%)
T#n LOW 편차
EUS(0.0~10.0%)
EUS
EUS(0.0%)
* #n : 1 ~ 6
①
②
③
④
⑤
[Figure 8-1] ON/OFF Signal Setup Screen