2nd Edition of TEMP2000_Series IM : July. 16. 2010 Page 50 / 87
5.2 UP, SOAK, DOWN Signal Operation
▶
Input Sensor = Temperature(K2), Range = -200.00℃ ~ 1370.00℃
▶
Up, Down Signal Range → [EUS 0% ~ EUS 10% ] = [ 0.00 ℃ ~ 20.00 ℃ ]
Setup
Up, Soak, Down Relay Operation according to Set Value
▶
Operation Type
→ Pattern Operation
▶ Up Temperature
→ 0.2 ℃
▶ Soak Temperature
→ 2 Minute
▶ Down Temperature
→ 0.2 ℃
▶ Fix Operation
Do not use
Change Rate
Operation
▶
Operation Type
→ Fix Operation
▶ Up Temperature
→ 0.2 ℃
▶ Soak Temperature
→ 2 Minute
▶ Down Temperature
→ 0.2 ℃
▶ Fix Operation
Do not use
Change Rate
Operation.
☞ Soak Signal Relay
does not become
ON for Fix
Operation. Only
Status Lamp is ON
at operation
screen.
Set Point(SP)
30.2℃
Up Temperature Set
ON
Down Temperature Set
Soak Set Time
2 Minute
30.0℃
50.0℃
49.8℃
Temp. Soak
Relay Output
Temp. Down
Relay Output
ON
ON
ON
Up Soak Down Soak
Set Point(SP)
30.2℃
Up Temperature Set
ON
Temp. Up
Relay Output
Down Temperature Set
30.0℃
50.0℃
49.8℃
Temp. Soak
Lamp Display
Temp. Down
Relay Output
ON
ON
ON
Set Point(SP)
Temp. Up
Relay Output