![Samwontech TEMI770 Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/samwontech/temi770/temi770_manual_3793449051.webp)
II.USERS
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 32/40
5-6-4-3. PID GROUP(PID1~PID9)
Figure 5-6-11 PID SET
①
OH.OL
: The range of controlled output
☞
Ex) OH.OL (OL < OH)
(Table 5-12) PID(PID1~PID9) PARAMETER
Name
Function
Valid Range
Unit
Default Value
P
PROPORTIONAL BAND
0.1 ~ 999.9
ABS
5.0
I
INTEGRAL TIME
0 ~ 6000
ABS
60
D
DERIVATIVE TIME
0 ~ 6000
ABS
240
T.OH
TEMP OUT LIMIT HIGH
0.0 ~ 100.0
ABS
100.0
T.OL
TEMP OUT LIMIT LOW
0.0 ~ 100.0
ABS
0.0
H.OH
HUMI OUT LIMIT HIGH
0.0 ~ 100.0
ABS
100.0
H.OL
HUMI OUT LIMIT LOW
0.0 ~ 100.0
ABS
0.0
PID1~PID9
①
105%
-5%
OL
OH
Controlled Range
0% 100%