![Samwontech TEMI770 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/samwontech/temi770/temi770_manual_3793449039.webp)
II.USERS
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 20/40
5-4-5. WAIT
Select
WAIT
at the Program page(Figure 5-4-1) for switching the WAIT page.
Figure 5-4-12 WAIT
①
WAIT USE : Set ON/OFF for using WAIT. All patterns are under WAIT function.
②
TEMP ZONE : Set a TEMP ZONE.
③
HUMI ZONE : Set a HUMI ZONE.
④
WAIT TIME : Set a WAIT TIME
(Table 5-6) WAIT PARAMETER
Name
Function
Valid Range
Unit
Default Value
WAIT USE
WAIT USE
OFF, ON
ABS
OFF
TEMP ZONE
TEMP WAIT ZONE
T.EUS(0 ~ 100%)
T.EUS
T.EUS(0%)
HUMI ZONE
HUMI WAIT ZONE
H.EUS(0 ~ 100%)
H.EUS
H.EUS(0%)
WAIT TIME
WAIT TIME
00.00 ~ 99.59
ABS
00.00
☞
Ex) Wait
If T.SP=90
℃
, wait area(TEMP.ZONE)=5
℃
then, wait zone is 85
℃
~95
℃
. When WAIT TIME=1H; PV
reach the wait area before WAIT TIME, work next segment, PV dose not reach the wait area before
WAIT TIME, it is waiting during WAIT TIME then go to next segment. It is or condition both of
TEMP.ZONE and HUMI.ZONE.
Figure 5-4-13 WAIT
3SEG
1SEG
95°
T.ZONE
T.ZONE
C
90°
85°
WAIT TIME=1H
2SEG
C
C
T.SV
T.PV
Wait time
2 SEG Working time