I. INSTALLATION
IM TEMI 770E_C 2nd Edition: Sep. 1. 2003. 13/15
4-2-6. Auxiliary Relay
CAUTION
If contact capacity is over 250VAC - resistance load 5A, 30VDC - resistance load 5A,
use auxiliary relay for ON/OFF load.
■
If you INDUCTANCE(L) load like as AUXILIARY RELAY or SOLENOIDE VALVE,
it might make go to wrong or out of order relay, please make sure insert to parallel circuit
with CR FILTER(AC) or DIODE(DC) by SURGE SUPPRESSOR of avoiding sparks.
■
Recommend CR FILTER
▶
Sung Ho Electronics
: BSE104R120 25V (0.1
μ
+120
Ω
)
▶
HANA PARTS CO.
: HN2EAC
▶
Songmi Electric Co., Ltd
: CR UNIT 953, 955 etc
▶
Jiwol Electric Co., Ltd.
: SKV, SKVB etc
▶
Shinyoung Communication Co., Ltd.
: CR-CFS, CR-U etc
(A) DC RELAY
(B) AC RELAY
R
RELAY
Out DC power
Machine
Use what a rated Relay Coil is must
be less than contact point capacity.
Connect Relay Coil socket directly
DIODE
R
RELAY
Out DC power
RC Filter
Use what a rated Relay Coil is must
be less than contact point capacity.
Connect Relay Coil socket directly