44
E901
E901
is an error with the outdoor unit, lower (inlet or return)
water heat exchanger sensor. It’s connected to a yellow plug on
the bottom right of the main PCB connector CN44 in a yellow
plug; it’s the top two wires
You can view this sensor
in the test mode from the
remote controller inside.
To access TEST mode press
blue
set
button
and
test
button together for 6
seconds.
The controller will display TEST.
Press the
blue view
button
once, a
temperature will be displayed and the word IN shows.
This is the reading from the sensor.
If you compare this with the actual water return temperature it should be exactly the same. If
they are different the sensor needs replacing.
To exit service mode press and hold
cancel delete
for 6 seconds