5. Electrical Connections
[Figure 5-19: PV connector (Female) and PV line (Male)]
The [Table 5-7] shows the lead wire standard for the PV. The thickness (6mm
2
) of the lead
wire is recommended for the 3.6 kWh All in One.
Area
Insulation
Color code
PE
6mm
2
600V or more
Green with yellow lines
PV (+), (-)
6mm
2
700V or more
Black
[Table 5-7: Wire Standard]
After opening the side cover, perform the PV and AC connection. (Refer to the contents
below). Disassemble the screw to open the side cover.
[Figure 5-20: Side cover opening]
The Male product is connected to the lead wire coming from the distribution box in the PV
side, and the Female part is attached to the All in One system. The two products are properly
docked when connected together. After opening the side cover, perform the PV and AC
connection.
38
Australia (Eng.) 05/2015. Rev1.1