5. Electrical Connections
5.
Electrical Connections
NOTICE
The 3.6 kWh All In One system can be damaged by static discharge.
Before you touch a component inside the 3.6 kWh All in One, ground
yourself by touching PE or a grounded object
CAUTION
When handling with the Li-Ion Battery Tray for the 3.6 kWh All in One, you
must wear the following personal protective equipment:
High voltage rated rubber gloves
Safety goggles or other protective eye equipment
40-minute standby period of time to complete discharging in the system
before testing electrical parts inside the system!
Follow the guidelines below when handling the Li-Ion Battery Tray.
Do not intentionally short circuit the positive (+) and negative (-) terminals
with a metallic object.
Do not remove the cap on the terminals. If the cap is removed, avoid
contact between the metals and the battery terminals. Do not damage the
screw thread.
Do not use seriously scarred or deformed battery. Dispose immediately
according to proper regulations.
Do not damage sheath of cable and connectors.