Troubleshooting
Samsung Electronics
4-17
■
Diagnosis and Adjustment (Error Code)
►
Error code related to the Communications / Settings / HW
(cont.)
Error mode
Cause
E-446
Error due to operation failure of Fan1
E-447
Motor wire of Fan1 is not connected
E-448
Lock error on Fan1
E-452
Error due to ZPC detection circuit problem or power failure
E-453
Error due to overheated motor of outdoor unit's Fan1
E-454
Error due to the outdoor unit fan RPM
E-455
Error due to the over heat Fan1 IPM
E-457
Outdoor unit Reversed direction of the wind Error
E-461
Error due to operation failure of inverter compressor 1
E-462
Compressor stop due to full current control or error due to low current on CT2
E-464
Error due to over-current of inverter compressor 1
E-465
V-limit error of inverter compressor 1
E-466
Error due to over voltage /low voltage of inveter PBA1
E-467
Error due to unconnected wire of compressor 1
E-468
Output current sensor error of inverter PBA1
E-469
DC voltage sensor error of inver PBA1
E-471
Error due to the INV1 Data Flash
E-474
Heat sink temperature sensor error of inverter PBA1
E-478
Error due to overcurrent of Fan1
E-483
Error due to over current of Fan1
E-485
Error due to input current of inverter 1
E-486
Error due to over voltage/low voltage of Fan
E-487
Hall IC error of Fan1
E-489
V-limit error on Fan1 of compressor
E-491
Error due to the Fan1 DataFlash
E-493
Output current sensor error of Fan1
E-496
DC voltage sensor error of Fan1
E-499
Heat sink temperature sensor error of Fan1
E-500
Error due to overheat caused by contact failure on IPM of Inverter PBA1
E-503
Error due to alert the user to check if the service valve is closed
E-504
Error due to self diagnosis of compressor operation
E-505
Error due to self diagnosis of high pressure sensor
E-506
Error due to self diagnosis of low pressure sensor
E-515
Error due to the over heat Control Box
E-516
Error due to the no feedback from the Fan of the control Box
E-552
Comp down due to the low discharge pressure
E-560
Outdoor unit's option switch setting error (when iinappropriate option switch is on)
E-563
Error due to module installation of indoor unit with old version (Micom version needs to be checked)
E-573
Error due to using single type outdoor unit in a module installation
E-702
Error due to closed EEV of indoor unit (1st detection)
E-703
Error due to opened EEV of indoor unit (1st detection)
UP
Auto Trial Operation incompleted (UnPrepared)
Содержание DVM S AM080FXVAGH
Страница 15: ...Samsung Electronics 2 9 2 1 3 Structure of product Heat Pump AM6666XV66H Series Small size Large size ...
Страница 199: ...Samsung Electronics 5 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN ...
Страница 202: ...5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB ŶAC 1 2 3 4 5 6 7 8 9 10 11 12 ...
Страница 204: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont ŶDC 1 1 2 3 4 5 6 7 8 9 10 11 ...
Страница 210: ...5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4 ...
Страница 212: ...5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6 ...
Страница 253: ...8 12 Samsung Electronics 8 3 How to check the view mode using a tact switch 㽞 AM080ί2606XV666 rX rY rZ r ...