CODE
Explanation
E-101
Indoor unit communication error. Indoor unit can not receive any data from outdoor unit.
E-102
Communication error between indoor unit and outdoor unit. Displayed in indoor unit.
E-108
Error due to repeated address setting (When 2 or more devices have same address within the network)
E-109
Incomplete communication error of indoor unit address
E-121
Error on indoor temperature sensor of indoor unit (Short or Open)
E-122
Error on EVA IN sensor of indoor unit (Short or Open)
E-123
Error on EVA OUT sensor of indoor unit (Short or Open)
E-128
EVA IN temperature sensor of indoor unit is detached from EVA IN pipe
E-129
EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe
E-130
Heat exchanger in/out sensors of indoor unit are detached
E-135
RPM feedback error of indoor unit's cleaning fan
E-149
Error due to AHU master indoor unit sensor setting.
E-151
Error due to opened EEV of indoor unit (2nd detection)
E-152
Error due to closed EEV of indoor unit (2nd detection)
E-153
Error on floating switch of indoor unit (2nd detection)
E-154
RPM feedback error of indoor unit
E-161
Mixed operation mode error of indoor unit; When outdoor unit is getting ready to operate in cooling (or
heating) and some of the indoor unit is trying to operate in heating (or cooling) mode
E-162
EEPROM error of MICOM (Physical problem of parts/circuit)
E-163
Indoor unit's remote controller option input is Incorrect or missing.
Outdo or unit EEPROM data error
E-180
Simultaneous opening of cooling/heating MCU SOL V/V (1st detection)
E-181
Simultaneous opening of cooling/heating MCU SOL V/V (2nd detection)
E-185
Cross wiring error between communication and power cable of indoor unit
E-186
Connection error or problem on SPi
E-190
No temperature changes in EVA IN during pipe inspection or changes in temperature is seen in indoor unit
with wrong address
E-191
No temperature changes in EVA OUT during pipe inspection or changes in temperature is seen in indoor
unit with wrong address
E-198
Error due to disconnected thermal fuse of indoor unit
■
Diagnosis and Adjustment (Error Code)
►
Error code related indoor unit
Содержание DVM S AM080FXVAGH
Страница 15: ...Samsung Electronics 2 9 2 1 3 Structure of product Heat Pump AM6666XV66H Series Small size Large size ...
Страница 199: ...Samsung Electronics 5 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN ...
Страница 202: ...5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB ŶAC 1 2 3 4 5 6 7 8 9 10 11 12 ...
Страница 204: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont ŶDC 1 1 2 3 4 5 6 7 8 9 10 11 ...
Страница 210: ...5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4 ...
Страница 212: ...5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6 ...
Страница 253: ...8 12 Samsung Electronics 8 3 How to check the view mode using a tact switch 㽞 AM080ί2606XV666 rX rY rZ r ...