Troubleshooting
4-8
Samsung Electronics
■
Auto Trial Operation
►
After initial installation, stable operation for a certain period of time limited to operation conditions.
Cooling
Heating
Method of Entry
K2 Tact Switch twice
K1 Tact Switch twice
Compressor
Normal operation, but the maximum frequency limit (differ by model)
Indoor Unit
Whole operation (The set temperature=3
°
C)
Whole operation (The set temperature=40
°
C)
Other Actuators
Normally control conduct
Operation time
Min : 60 minutes, Max : 10 hours
Etc.
∙ Exceed the maximum operating time at stops and waits.
∙ Protection and control, self-diagnosis is performed.
■
Refrigerant filling operation
►
Operation to filling the refrigerant compressor was fixed at a certain frequency.
Cooling
Heating
Method of Entry
K2 Tact Switch one time
K1 Tact Switch one time
Compressor
Starting frequency (Mild Start frequency) operation
Indoor Unit
Whole operation (The set temperature=3
°
C)
Whole operation (The set temperature=40
°
C)
Other Actuators
Normally control conduct
Operation time
60 minutes
Etc.
During the filling operation does not enter the special operation, such as oil recovery.
Содержание DVM S AM080FXVAGH
Страница 15: ...Samsung Electronics 2 9 2 1 3 Structure of product Heat Pump AM6666XV66H Series Small size Large size ...
Страница 199: ...Samsung Electronics 5 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN ...
Страница 202: ...5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB ŶAC 1 2 3 4 5 6 7 8 9 10 11 12 ...
Страница 204: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont ŶDC 1 1 2 3 4 5 6 7 8 9 10 11 ...
Страница 210: ...5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4 ...
Страница 212: ...5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6 ...
Страница 253: ...8 12 Samsung Electronics 8 3 How to check the view mode using a tact switch 㽞 AM080ί2606XV666 rX rY rZ r ...