Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When power is not supplied to the indoor unit, there should be additional source of power supply to the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Depending on the installation condition, set the installation option of the indoor unit.
- The default setting value of the indoor unit installation option is “020010-100000-200000-300000”.
- Individual control setting (SEG20) is the function that controls an indoor unit individually when there is more than one
indoor unit.
4. Set the indoor unit option by using a remote controller.
02 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
External room
temperature sensor /
Minimizing fan
operation when
thermostat is off
Central control
-
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
-
-
-
EEV Step when
heating stops
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output / External heater
On or Off signal
S-Plasima ion
Buzzer
-
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control
of a remote
controller
Heating setting
compensation /
Removing condensated
water in heating mode
Oil return / EEV
opening step in
defrost mode
-
Louver Swing
Speed
f
When setting the option other than above SEG values, the option will be set as “0”.
f
SEG5 central control option is basically set as 1(Use), so you don’t need to set the central control option additionally to use
the central control function. However, if the central control is not connected but it doesn’t indicate an error message or if
the indoor unit needs to be excluded from the central control, you need to set the central control option as 0 (Disuse).
f
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
ENGLISH-25