Option SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
Page
Individual control of
a remote controller
Heating setting compensation /
Removing condensated water in heating
mode
EEV Step of stopped unit
during oil return/defrost
mode
-
Louver Swing Speed
Remote
controller
display
-
-
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication Details Indication
Details
Heating Setting
Compensation
Removing
Condensated
Water in Heating
Mode
3
0 or 1
Channel 1
0
Default
(*3)
Disuse
0
Default
value
-
0
Default 18 ms
1
2 °C Disuse
1
Oil return
or noise
decreasing in
defrost mode
1
27 ms
2
Channel 2
2
5 °C
Disuse
2
24 ms
3
Channel 3
3
Default
(*3)
Use
(*4)
3
21 ms
4
Channel 4
4
2 °C
Use
(*4)
4
18 ms
5
15 ms
5
5 °C
Use
(*4)
6
12 ms
7
9 ms
(*1)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
(*2)
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will
not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fix it as
cool mode.
❋
*G'BOJTTFUUPPòGPSDPPMJOHPOMZJOEPPSVOJUCZTFUUJOHUIF4&(PS4&(ZPVOFFEUPVTFBOFYUFSOBMTFOTPSPS
wired remote controller sensor to detect indoor temperature exactly.
(*3)
Default setting value
- 4Way Cassette, Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
(*4)
This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the heating
mode immediately after finishing the cooling mode, the condensated water in the drain pan becomes water vapor by the
heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may fall into
a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum
20 minutes) even when the indoor unit is turned off after cooling mode is turned to heating mode.
t
Do not install the electronic heater in the flow channel of the indoor unit fan.
Air Flow
Suction side
Discharge side
Electronic heater should not
be installed.
Duct Indoor unit
CAUTION
Setting an indoor unit address and installation option
ENGLISH-27
02
INST
ALLA
TION
Содержание AM140RNPDKH Series
Страница 36: ...DB68 08452A 00...