temperature and, if applicable, other data points can be retrieved and displayed.
The room panel is connected to terminals 27 to 30 as illustrated in Fig. 11.
Functions
WE
Configuration
Device bus
0
CO7 -> F01 - 1; device bus address
TROVIS 5570 Room Panel in RK1
0
CO7 -> F03 - 1; device bus address
TROVIS 5570 Room Panel in RK2
0
CO7 -> F04 - 1; device bus address
Note!
The room panel can only be supplied by the controller when no meter bus plug-in module is
installed.
7.12.6 Display error alarms issued by the device bus
Error alarms over device bus do cause controllers with an active modem function already in
the default setting to dial the control station. However, the error alarms issued by the device
bus are not displayed by controllers configured in this way. The setting CO7 -> F16 - 1
causes these controllers to react to the error alarms from the device bus by generating an
“Err 5” alarm as long as the faults of the other device bus participants exist. The black
84
EB 5576 EN
System-wide functions
12...26.5V AC/
15...36V DC
BA12
BA13
UP1 On/off
UP1 Speed
Pump management - COM
COM BA12, BA13
Y COM
TROVIS 5576
TROVIS 5570
Y1
Y2
0...10V
0...10V
16
18
20
22
15
17
19
21
23
24
26
28
30
25
27
29
14
1
2
3
4
5
6
7
8
9
Fig. 11 · Connecting the TROVIS 5570 Room Panel to the controller