Function block parameters
/ Range of values (default)
19 Time-controlled
switchover of
storage tank
sensors
0
Not Anl
11.0, 11.3
CO4 -> F19 - 1 only with CO4 -> F02 - 1
SF1 for day mode and SF2 for night mode.
20 DHW circuit
additionally
controlled by a
globe valve
0
7.1, 8.1,
11.1
CO4 -> F20 - 1: Return flow temperature limitation over a
globe valve with VF2 in the heating register return pipe of
the storage tank.
F Function block number, WE Default value, Anl System code number
CO5: System-wide functions
(all systems)
If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity settings
are locked.
F Function
WE
Anl
Comment
Function block parameters
/ Range of values (default)
01 Sensor calibration
1
All
CO5 -> F01 - 1 and CO5 -> F02 - 0: Pt 1000 (Pt 100)
CO5 -> F01 - 0 and CO5 -> F02 - 0: PTC (Pt 100),
CO5 -> F01 - 0 and CO5 -> F02 - 1: NTC (Pt 100)
CO5 -> F01 - 1 and CO5 -> F02 - 1: Ni 1000 (Pt 100)
02
0
All
03 Reserved
04 Summer mode
0
All
CO5 -> F04 - 1:
Activation of time-controlled summer mode
Function block parameters:
Start summer mode / 01.01 to 31.12 (01.06)
No. of days until activation / 1 to 3 (2)
Stop summer mode / 01.01 to 31.12 (30.09)
No. of days until deactivation / 1 to 3 (1)
OT limit value summer mode / 0 to 30 °C (18 °C)
05 Delayed OT
adaptation when
OT decreases
0
All
CO5 -> F05 - 1:
Function block parameter:
Delay / 1 to 6 °C/h (3 °C/h)
06 Delayed OT
adaptation when
OT increases
0
All
CO5 -> F06 - 1:
Function block parameter:
Delay / 1 to 6 °C/h (3 °C/h)
07 Fault indication
output BA13
0
All
With CO5 -> F07 - 1, the pump management function is not
available
EB 5576 EN
113
Appendix