Appendix
12.1 Function block lists
CO1: Heating circuit RK1
F Function
WE
Anl
Comment
Function block parameters
/ Range of values (default)
01 Room sensor RF1
0
Not in Anl
1.5-1.8,
3.x, 7.x
CO1 -> F01 - 1: Temperature display and input FG1 for
Type 5244/5257-5 Room Panel active
TROVIS 5570 Room Panel:
CO1 -> F01 - 1
and
CO7 -> F03 - 1
02 Outdoor sensor
AF1
1
Not in Anl
1.5-1.8,
7.x
CO1 -> F02 - 1: Weather-compensated control active
Outdoor temperature received via device bus:
CO1 -> F02 - 1
and
CO7 -> F07 - 1
03 Return flow sensor
RüF1
0
1.2, 1.4,
10.2
CO1 -> F03 - 1: Sensor and limiting function active
Function block parameter:
Limiting factor / 0.1 to 10.0 (1.0)
1
Not in Anl
1.2, 1.4,
10.2
04 Reserved
05 Underfloor heating
Drying of jointless
floors
0
Not in Anl
1.5-1.8,
3.x, 7.x
CO1 -> F05 - 1: Limitation of the adjustment ranges
Function block parameters:
Temperature rise / 1 to 10 °C/24 h (5 °C/24 h)
Maximum temperature / 25 to 60 °C (45 °C)
Maintaining time of max. temperature/1 to 10 days (4 days)
Temperature reduction / 0 to 10 °C/ 24 h (0 °C / 24 h)
START
06 Reserved
07 Optimization
0
Not in Anl
1.5-1.8,
3.x, 7.x
CO1 -> F07 - 1: Only with
•
CO1 -> F01 - 1
•
CO1 -> F02 - 1
08 Adaptation
0
Not in Anl
1.5-1.8,
3.x, 7.x
CO1 -> F08 - 1: Only with
•
CO1 -> F01 - 1
•
CO1 -> F02 - 1
•
CO1 -> F11 - 0
09 Flash adaptation
0
Not in Anl
1.5-1.8,
3.x, 7.x
CO1 -> F09 - 1: Only with CO1 -> F01 - 1
Function block parameter:
Cycle time / 1 to 100 min (20 min)
10 Reserved
0
EB 5576 EN
107
Appendix