Systems Anl 3.1 to 3.4
System
Anl 3.1
Anl 3.2
Anl 3.3
Anl 3.4
Type of DHW heating
Type 1
Type 2
Type 3
Type 4
1)
XX =
SLP
UP1
SLP
UP1
Integration of flow sensor VF4
Not possible
Possible
Not possible
Possible
ZP integration with CO4 ->
F10 - 1 (broken line, see cover)
–
Not possible
–
Not possible
Note
–
–
Binary output
BA9 replaced
by UP1
Only
0 to 10 V
output signal
available (Y2)
Default settings
CO1 -> F02
- 1 (with AF1)
- 1 (with AF1)
- 1 (with AF1)
- 1 (with AF1)
CO1 -> F03
- 1 (with RüF1)
- 1 (with RüF1)
- 1 (with RüF1)
- 1 (with RüF1)
CO2 -> F01
- 0 (w/o RF2)
- 0 (w/o RF2)
- 0 (w/o RF2)
- 0 (w/o RF2)
CO2 -> F03
- 0 (w/o RüF2)
- 0 (w/o RüF2)
- 0 (w/o RüF2)
- 0 (w/o RüF2)
CO4 -> F01
- 1 (with SF1)
- 1 (with SF1)
- 1 (with SF1)
- 1 (with SF1)
CO4 -> F02
- 0 (w/o SF2)
- 1 (with SF2)
- 0 (w/o SF2)
- 1 (with SF2)
CO4 -> F05
- 0 (w/o VF4)
- 0 (w/o VF4)
EB 5576 EN
37
Systems
BE
BA
AE
AA
AF1
RüF1
VF1
UP2
RK2/Y2
RK1/Y1
RF2
VF2
RüF2
XX
1)
DHW
heating
Unfold back cover!