Parameters
WE
Parameter level / Range of values
Reduced flow temperature
Point 1
Point 2
Point 3
Point 4
60 °C
40 °C
20 °C
20 °C
PA1, 2 / 5 to 130 °C
Return flow temperature
Points 1 to 4 65 °C
PA1, 2 / 5 to 90 °C
Min. flow temperature
20 °C
PA1, 2 / 20 to 130 °C
Max. flow temperature
90 °C*
PA1, 2 / 20 to 130 °C
* With CO1, 2 -> F05 - 1, the following applies: Max. flow temperature / 5 to 50 °C (50 °C)
Note!
The
4-point characteristic
function can only be activated when the
Adaptation
function is not
active (CO1, 2 -> F08 - 0).
5.2
Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed set
point. Outside the times-of-use, the controller regulates to a reduced flow temperature.
Set the desired rated flow temperature as
Day set point, and the reduced flow temperature
as
Night set point.
Functions
WE
Configuration
Outdoor sensor AF1
1
CO1 -> F02 - 0
Parameters
WE
Rotary switch / Range of values
Day set point
50 °C
Top, middle / Min. to max. flow temperature
Night set point
30 °C
Top, middle / Min. to max. flow temperature
Parameters
WE
Parameter level / value range
Min. flow temperature
20 °C
PA1, 2 / 5 to 130 °C
Max. flow temperature
90 °C
PA1, 2 / 5 to 130 °C
Note!
A fixed set point control in heating circuit 2 with CO2 -> F02 - 0 can only be configured if
CO1 -> F02 - 0 is set as well, because the heating circuit 2 with CO2 -> F02 - 0 only uses
the measured outdoor temperature provided by heating circuit 1.