Parameters in level 5
Parameters (PA5)
Level 5
Range of values
Public holidays
01.01 to 31.12
Vacation periods, start
01.01 to 31.12
Vacation periods, stop
Assignment to control circuit
RK1, RK2, RK4
Vacation periods, start
01.01 to 31.12
Vacation periods, stop
Assignment to control circuit
RK1, RK2, RK4
Function block parameters (CO5)
Start summer mode (F04 - 1)
01.01 to 31.12
No. of days until activation (F04 - 1)
1 to 3
Stop summer mode (F04 - 1)
01.01 to 31.12
No. of days until deactivation (F04 - 1)
1 to 3
OT limit value summer mode (F04 - 1)
0 to 30 °C
Delay (F05/6 - 1)
1 to 6 °C/h
Frost protection limit (F09 - 1)
–15 to 3 °C
Max. limit value (F10 - 1)
3 to 500
pulse
h
Max. limit value for heating (F10 - 1)
3 to 500
pulse
h
Max. limit value for DHW (F10 - 1)
3 to 500
pulse
h
Limiting factor (F10 - 1)
0.1 to 10.0
Lower measuring range value (F11 - 1)
0/4 mA
Upper range value 20 mA (F11 - 1)
0.01 to 650
m
h
3
Max. limit value (F11 - 1)
0.01 to 650
m
h
3
Max. limit value for heating (F11 - 1)
0.01 to 650
m
h
3
Max. limit value for DHW (F11 - 1)
0.01 to 650
m
h
3
Limiting factor (F11- 1)
0.1 to 10.0
Binary input bE (F12 - 1)
1, 0
EB 5576 EN
137