80
EB 8384-4 EN
Adjusting the limit switch
9 Adjusting the limit switch
The positioner version with an inductive limit
switch has an adjustable tag (1) mounted on
the axis of rotation, which operates the prox-
imity switch (3).
For operation of the inductive limit switch,
the corresponding switching amplifier (see
section 5.2.1) must be connected to the out
-
put circuit.
When the tag (1) is located in the inductive
field of the switch, the switch assumes a high
resistance. When it moves outside the field,
the switch assumes a low resistance.
Normally, the limit switch is adjusted in such
a way that it will provide a signal in both
end positions of the valve. The switch, how-
ever, can also be adjusted to indicate inter-
mediate valve positions.
Metal tag (1)
Proximity switch (3)
Adjustment screw (2)
Fig. 25:
Adjusting the limit switch
Содержание 3730-4
Страница 17: ...EB 8384 4 EN 17 Design and principle of operation...
Страница 105: ...EB 8384 4 EN 105...
Страница 106: ...106 EB 8384 4 EN...
Страница 107: ...EB 8384 4 EN 107...
Страница 108: ...108 EB 8384 4 EN...
Страница 109: ...EB 8384 4 EN 109...
Страница 110: ...110 EB 8384 4 EN...
Страница 111: ...EB 8384 4 EN 111...
Страница 112: ...112 EB 8384 4 EN...
Страница 113: ...EB 8384 4 EN 113...
Страница 123: ...EB 8384 4 EN 123...
Страница 124: ...124 EB 8384 4 EN...
Страница 125: ...EB 8384 4 EN 125...