72
EB 8384-4 EN
Start-up and settings
Change pressure limit and control parame-
ters:
Do not change the pressure limit (Code 16).
Only change the control parameters K
P
(Code 17) and T
V
(Code 18) if the settings of
the the replaced positioner are known.
Pressure limit
Default:
No
K
P
level
Default
7
T
V
level
Default
2
Turn
Code 16/17/18
Press
, Code 16/17/18 blinks.
Turn to set the control parameter select-
ed.
Press
to confirm the setting.
Enter closing direction and blocking position:
Closing direction (direction of
rotation causing the valve to
move to the CLOSED position
(view onto positioner display)
Default: CCL (counterclockwise)
mm
Blocking position
Default
0
Turn
Code 34
Press , Code 34 blinks.
Turn
Closing direction (CCL = counter
-
clockwise/CL = clockwise)
Press .
Turn
Code 35
Press , Code 35 blinks.
Turn
Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Set the fail-safe position:
Î
Set switch for closed position AIR TO
OPEN or AIR TO CLOSE according to
section 7.1.
Î
Set volume restriction as described in
section 7.2.
Start initialization:
Î
Press INIT key.
The positioner switches to MAN mode.
The blocking position is indicated.
Note
Содержание 3730-4
Страница 17: ...EB 8384 4 EN 17 Design and principle of operation...
Страница 105: ...EB 8384 4 EN 105...
Страница 106: ...106 EB 8384 4 EN...
Страница 107: ...EB 8384 4 EN 107...
Страница 108: ...108 EB 8384 4 EN...
Страница 109: ...EB 8384 4 EN 109...
Страница 110: ...110 EB 8384 4 EN...
Страница 111: ...EB 8384 4 EN 111...
Страница 112: ...112 EB 8384 4 EN...
Страница 113: ...EB 8384 4 EN 113...
Страница 123: ...EB 8384 4 EN 123...
Страница 124: ...124 EB 8384 4 EN...
Страница 125: ...EB 8384 4 EN 125...