EB 8384-4 EN
69
Start-up and settings
Turn
Pin position on lever (see relevant
section on attachment)
Press .
Turn
Code 5
Press , Code 5 blinks.
Turn
Nominal travel of the valve
Press .
Select the initialization mode:
Init mode
Default
MAX
Turn
Code 6
Press
, Code 6 blinks.
Turn
NOM
Press
to confirm the NOM as the initial
-
ization mode.
Start initialization:
Î
Press INIT key.
Î
After initialization, check the direction of
action (Code 7) and, if necessary,
change it.
7.6.3 MAN – Initialization
based on a manually
selected range
Before starting initialization, move the con
-
trol valve manually to the OPEN position.
Turn the rotary pushbutton ( ) clockwise in
small steps. The valve must be moved with a
monotonically increasing signal pressure.
The positioner calculates the differential trav-
el/angle from the OPEN and CLOSED posi
-
tions and adopts it as the operating range
with limits of lower travel/angle range value
(Code 8) and upper travel/angle range val
-
ue (Code 9).
Enable configuration:
If no settings are entered within 120 sec
-
onds, the enabled configuration function be
-
comes invalid.
Enable configuration
Default:
No
Turn
g
Code 3, display: No
Press , Code 3 blinks.
Turn
YES
Press , display:
Enter the pin position:
mm
Pin position
Default:
No
Turn
Code 4
Press , Code 4 blinks.
Turn
Pin position on lever (see relevant
section on attachment)
Press .
Note
Содержание 3730-4
Страница 17: ...EB 8384 4 EN 17 Design and principle of operation...
Страница 105: ...EB 8384 4 EN 105...
Страница 106: ...106 EB 8384 4 EN...
Страница 107: ...EB 8384 4 EN 107...
Страница 108: ...108 EB 8384 4 EN...
Страница 109: ...EB 8384 4 EN 109...
Страница 110: ...110 EB 8384 4 EN...
Страница 111: ...EB 8384 4 EN 111...
Страница 112: ...112 EB 8384 4 EN...
Страница 113: ...EB 8384 4 EN 113...
Страница 123: ...EB 8384 4 EN 123...
Страница 124: ...124 EB 8384 4 EN...
Страница 125: ...EB 8384 4 EN 125...