12
➃
DIP switch settings
DIP switch 1 and 2 are used select the desired charge program for
the connected output battery. Please see the table below:
¹⁾ Charge voltage value
between brackets are
for EL 12-24/30 model.
²⁾ All standard charge
voltage values are
configurable using
the Samlex Dashboard
and Dashboard Mobile
apps.
DIP1
DIP2
Battery type / Charge program ¹⁾ ²⁾
Off
Off
Flooded (default setting)
Bulk/Abs voltage = 14.4V (28.8V)
Float voltage = 13.5V (27.0V)
Off
On
GEL
Bulk/Abs voltage = 14.2V (28.4V)
Float voltage = 13.5V (27.0V)
On
Off
AGM
Bulk/Abs voltage = 14.7V (29.4V)
Float voltage = 13.6V (27.2V)
On
On
LiFePo4
Bulk/Abs voltage = 14.4V (28.8V)
Float voltage = 13.8V (27.6V)
DIP switch 3 is reserved for future use (default off).
DIP switch 4 can be used to bypass the On/Off control input (see point 3 above). When this
DIP switch is set to On (default setting), the On/Off control input is bypassed and the charger
will always operate, independent of the status at the control input. When this DIP switch is set
to Off, the charger is controlled by the On/Off control input. This setting is recommended for
vehicle applications with a proper engine run signal.
CAUTION
Invalid battery type settings can cause serious damage to your batteries and/or
connected battery loads. Always consult your battery’s documentation for the correct
charge voltage settings.