Sirius 800 Series User Manual
Input Modules
Modules No Longer Supplied With New Systems C.2
Iss 5 Rev 7
Page 311
© 2017 SAM
C.2.1.1
5913/5914 Input Module LED Information
Table 95 shows the LED color code on the 5913 and 5914 input modules, and Figure 199
shows the input module LEDs on the edge of the module.
LED Color Function
Detail
Normal Working Status
Green
Power OK
Power to the module
On Solid
- working correctly
Yellow
Local
Command
OK
Receiving messages
from local Nucleus
control module (the
Nucleus controller in
this frame)
Flashing
- receiving information and
working correctly
Red
Local Error Error with messages
from local Nucleus
control module (the
Nucleus controller in
this frame)
Off
- normal state
Flashing
- the command message from
the router controller is corrupt or hasn’t
been received.
This communications error could be
caused by a hardware failure or incorrect
insertion. Check that the module is
inserted correctly.
If the “Local Error” LED is flashing at the
same time as the “Local Command OK”
LED is flashing it suggests a mismatch in
the configuration of the Nucleus controller.
Check the controller configuration.
Yellow
Remote
Command
OK
Receiving messages
from remote Nucleus
control module (the
Nucleus controller in the
frame linked to this
frame)
Sirius 830/840/850 (no expansion)
:
Off
- Expansion not used.
Sirius 850 (expanded to second frame)
:
Flashing
- receiving information and
working correctly
Red
Remote
Error
Error with messages
from remote Nucleus
control module (the
Nucleus controller in the
frame linked to this
frame)
Sirius 830/840/850 (no expansion)
:
Off
- Expansion not used.
Sirius 850 (expanded to second frame)
:
Off
- normal state,
Flashing
- the command message from
the remote router controller is corrupt or
hasn’t been received.
This communications error could be
caused by a hardware failure a or
incorrect insertion. Check that the module
is inserted correctly and the four RJ45
connections between the frames are fitted
correctly (see section 12.2).
If the “Remote Error” LED is flashing at
the same time as the “Remote Command
OK” LED is flashing it suggests a
mismatch in the configuration of the
Nucleus controller. Check the controller
configuration.
Table 95
5913/5914 Sirius 840/850 Standard Video Input Module LED Information