Single Active IP Addr. on Dual Red. Controllers (Optional)
Nucleus Router Control Modules 14.3
Iss 5 Rev 7
Page 259
© 2017 SAM
14.3.5 SAM Control Panel(s) over IP:
When control panels are connected over IP to router controllers that are configured with a
single active IP address it is important that the control panels are configured to connect to the
single active IP address of the Nucleus control Modules and that no secondary control system
IP address is set. The following Snell control panel settings are recommended:
•
Control System IP address #1: 172.31.9.30 (assuming this is the Active IP Address)
•
Control System IP address #2: Blank
The configuration procedure varies depending on the control panel type being configured.
See the appropriate control panel manual for configuration details.
In this example
:
•
The control panel is only configured with the active IP address. If the Nucleus control
Module fails or is manually reset the previously idle router controller will failover and
go active. At this point the control panel will connect to the now active router controller
using the active IP address.
Note:
These parameters are called Router Connection Primary IP Address and Router
Connection Secondary IP Address on some control panel types.