Remove the AC BACK-UP connector from the accessory bag.
6.
Insert the ends of the four cables into the corresponding
holes on the connector: cables for phases R, S, T into the R,
S, T ports and neutral into the N port. Make sure the cables
reach the back of the connector and screw them in tightly. Pull
slightly on the cable to check that it is properly connected.
7.
Connect the AC BACK-UP connector to the AC BACK-UP
terminal on the inverter, as shown in Fig. 56 below:
Fig. 56. AC BACK-UP connection.
8.
Place the housing in its position and secure it using the
4 screws included in the package.
9.
Insert the relevant AC circuit breakers in between, as shown
in the table below:
Model
Thermal-
magnetic
circuit
breaker
Dif-
ferential
relay
Over-
voltage
protection
Previous
fuse. Max.
value
(1/phase)
EQX2 4002-HT
4P 10 A C
curve
4P 25 A
30 mA
Class A
Type II 40 kA
400 V TT
125 A gL
EQX2 5002-HT
EQX2 6002-HT
4P 16 A C
curve
EQX2 8002-HT
EQX2 10002-HT
4P 20 A C
curve
4P 32 A
30 mA
Class A
EQX2 12002-HT
4P 25 A C
curve
Tab. 18. AC circuit breakers.
10.
Connect the other end of the bundle to the AC circuit breakers
for the critical BACK-UP loads.
Fus.
PIAs
Back-up
ID
MCB
SPD
Inverter
Fig. 57. Complete diagram of the AC BACK-UP connections.