Airfield Lighting
Safegate Group
Manual
Date: October 2016
Ref: SL-RE-E_SL-RT-E_SL-RN-E_SL-RTN-E_SL-SB-E
Version: 1.4
Page 30 of 42
3.2.2
Programming the Software
ASP-SC Maintenance Tool (AMT) software is required for SafeLED IQ product
configuration. The following are instructions how to use AMT software (version 3.3 or
later) for SafeLED IQ product configuration.
Program a SafeLED IQ product
1. Make sure the Remote button on the LPC is NOT
pressed in (off) before you start programming.
2. Start the AMT program on the PC and
if
Can’t open COM port
appears, click
OK
.
FIGURE 37
– AMT START
3. Enter the following information:
Enter Username: for example,
guest
Enter Password: ******** for example,
safegate
Note: User name and password may differ.
4. Click
OK
.
FIGURE 38
– AMT LOGIN
5. Chose the text file with the required airport and
light fixture to use.
6. Select the file and click
Open
.
FIGURE 39
– AMT TEXT FILE