Airfield Lighting
Safegate Group
Manual
Date: October 2016
Ref: SL-RE-E_SL-RT-E_SL-RN-E_SL-RTN-E_SL-SB-E
Version: 1.4
Page 32 of 42
Program a SafeLED IQ product
12.
From the LPU Manager tab, enter the
PID Number
in the text field, manually or using a bar code
reader.
Note: The number corresponds to the product
information number found on the bottom of the
SafeLED IQ, as in the previous step.
FIGURE 43
– AMT ENTER PID
13. Click
Download Parameters
, to start an automatic
parameter download.
FIGURE 44
– AMT DOWNLOAD PARAMS
14. Click
Continue
to confirm parameter download.
15. The SCM unit should now sound and configuration
progress information appears in the log at the
bottom of the window.
Note: If there is no sound from the SCM during
configuration, check settings for example COM
port or cables.
16. When downloading the parameters is complete, a
checksum check starts to ensure the SafeLED IQ
has received the new parameters without fault.
If the unit without fault,
click
OK
and the unit is now ready to use.
17. Disconnect the SafeLED IQ product cable.
18. Turn off the SCM, LPC for at least 30 seconds to
fully power down the SafeLED IQ or when no more
SafeLED IQ products are to be configured.
19. Turn on the LPC to power up the SafeLED IQ, for
example an RGL, set to flash as default, should
flash.
FIGURE 45
– AMT CONFIRM PARAMS
FIGURE 46
– AMT CHECKSUM