106
English
“PAr”
DESCRIPTION
RANGE
DEFAULT
QLO
Minimum flow rate
88
-108
98
QHI
Maximum flow rate
243
- 270
270
nLO
Minimum rpm in operation
90 - 110
100
nHI
Maximum speed
2610 - 3190
2900
Pstd
Percentage of standard modulation of nominal speed
100% - 110%
100%
PbSt
Percentage of boost/party modulation
110% - 130%
130%
PnGt
Percentage of night modulation
45% - 100%
70%
PMEd
Percentage of intermediate modulation
35% - 70%
45%
PHOL
Percentage of minimum - holiday modulation
0 - 35%
25%
TPrt
PARTY duration time
15 - 240 min
180
TbSt
Boost duration time
15 - 240 min
180
TCOOL
Cooling setpoint temperature for free-heating management
10 - 35°C
26
THEAt
Heating setpoint temperature for free-cooling management
10 - 35°C
20
BPASS
Parameter for overriding free-heating logics
FCFH/FC
FCFH
TESt
Summer season transition temperature for pre-cooling management
geothermal coil
10 - 35°C
24
TInv
Winter season transition temperature for antifreeze management
geothermal coil
10 - 35°C
18
RrEFt
Reference temperature for antifreeze functions
T1 or T4
T1
TPrEF
Post-treatment reference temperature
T3 or T2
T3
SPrC
Percentage imbalance between flow rates
-30% - +30%
0%
RHnSP
Number of samples to calculate dynamic humidity setpoint
1 - 96
96 (15 min)
FLIFE
Filter service life
30 - 360 days
180 days
CO2Hi
Maximum CO2 level *
1500 - 2000 ppm
1500
CO2lo
Minimum CO2 level *
400 - 600 ppm
500
CO2St
Nominal CO2 level *
900 - 1100 ppm
1000
CO2Sr
Full-scale CO2 *
2000 - 30000 ppm
2000
HrLO
Relative humidity for Minimum Humidity mode activation
Relative humidity lower limit in the comfort range
20 - 45
25
HrSt
Relative humidity upper limit in the comfort range
40 - 50
45
HrHiF
Activates the display of parameter
HrHi
On - Off
Off
HrHi
Relative humidity for Maximum Humidity mode activation
60 - 80
65
MrHS
Logic activation with single humidity sensor
On - Off
OFF
FLUSH
Activation of forced summer exchange mode
On - Off
OFF
ErHS
Speed in case of Minimum Humidity mode
1st - 4th speed
2nd speed
FUnC
FUNCTIONS blocking operation (see dedicated paragraph)
-
-
MStOP
If On, speed 1 set in the weekly program is the same as switching off the unit
On - Off
OFF
P
Default weekly program setting
-
-
* Available only if the functions feature air quality sensors