107
English
“PAr”
DESCRIPTION
RANGE
DEFAULT
T2StH
Fixed-point post-heating setpoint temperature
Visible if “Tpref” is the same as T2
10 - 50°C
25
T2StC
Fixed-point post-cooling setpoint temperature
Visible if “Tpref” is the same as T2
10 - 50°C
22
T3StH
Ambient air conditioning post-heating setpoint temperature
Visible if “Tpref” is the same as T3
10 - 50°C
20
T3StC
Ambient air conditioning post-cooling setpoint temperature
Visible if “Tpref” is the same as T3
10 - 50°C
26
POSt
Type of post-treatment if DIP 4 and DIP 5 are ON
All / Cool
All
HS1
Post-heating coil activation hysteresis parameter -
First stage
0 - 2
0.5
HS2
Post-heating coil activation hysteresis parameter -
Second stage
0 - 2
0.5