UNIT CONFIGURATION DIP SWITCH (DIP 1)
DIP NO.
DEFAULT
OFF
ON
1
OFF
LEFT
flow config
RIGHT
flow config
2
OFF
No Pre-Treatment Air
Pre-Treatment Air Present
3
OFF
If DIP2 ON
Modulating Electric Heater
If DIP2 ON and
DIP7 OFF
Electric Heater ON/OFF
Hot water coil with ON/OFF valve
4
OFF
No Post-Treatment Air
Post-Treatment Air Present
5
OFF
No Post-Cooling Air
Post-Cooling Air Present
6
OFF
FC-FC Digital Output
“NO” Contact for Alarm warning status
(see table paragraph “ALARMS”)
FC-FC Digital Output
“NO” Contact : it gets closed when the ventilation is active
7
OFF
No Geothermal Hydronic Coil
If DIP2 and DIP3 ON
Geothermal Hydronic Coil Present
8
OFF
Contact C3-C3 with function that prevents
negative ambient pressure in presence of chimney
Contact C3-C3
with atmospheric boiler start-up booster
RS485-B CONFIGURATION DIP SWITCH (DIP3)
DIP N. 1
DIP N. 2
Operation with T-EP display control
(Default)
ON
OFF
Operation as Slave Modbus
OFF
ON