RYMASKON 600 Series | Parameter Table | Last Updated: 23/03/2022 (EN)
7
FAN, BOOST, LIGHTS AND BLINDS
Parameter name
Description
Range
Light Interlock
Locks the lighting
(1) Disabled
Light intensity is maintained when toggling between
comfort (standard mode) and ECO/OFF
(2) Comfort
•
ECO/OFF
à
Comfort (standard mode):
Light intensity 100%
•
Comfort (standard mode)
à
ECO/OFF:
Light intensity 0%
•
Priority switching by hand or via the bus;
maintained in ECO/OFF mode
(3) C ECO
•
ECO/OFF
à
Comfort (standard mode):
Light intensity 100%
•
Comfort (standard mode)
à
OFF:
Light intensity 0%
•
Comfort (standard mode)
à
ECO:
Light intensity remains unchanged
•
Priority switching by hand or via the bus;
maintained in ECO/OFF mode
(see chapter “Blind and Light icons”)
0 = Disabled (Default)
1 = Comfort
2 = C ECO
ALARMS
Parameter name
Description
Range
Alarm 1 Source
Source for alarm indicator, alarm 1
0 = CO2 sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
Alarm 1 Amber Threshold
Switching point for amber alarm indicator, alarm 1
0...5000 (default 0)
Alarm 1 Red Threshold
Switching point for red alarm indicator, alarm 1
0...5000 (default 0)
Alarm 1 Hysteresis
Hysteresis for alarm 1
0...5000 (default 0)
Alarm 2 Source
Source for alarm indicator, alarm 1
0 = CO2 sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
Alarm 2 Amber Threshold
Switching point for amber alarm indicator, alarm 1
0...5000 (Default 0)
Alarm 2 Red Threshold
Switching point for red alarm indicator, alarm 1
0...5000 (Default 0)
Alarm 2 Hysteresis
Hysteresis for alarm 2
0...5000 (Default 0)
SYSTEM
Parameter name
Description
Range
Address
Configuring the bus address
Modbus: 0...247 (Default 1)
BACNet: 0...127 (Default 1)
Baud rate
Baud rate for Modbus or BACnet units
0 = 9600 (Default)
1 = 19200
2 = 38400
3 = 57600
4 = 76800
Parity
Parity for Modbus or BACnet units
0 = None (Default)
1 = Odd
2 = Even
Stop Bits
Stop bits for Modbus or BACnet units
0 = 1 Stop Bit (Default)
1 = 2 Stop Bits