S+S REGELTECHNIK GMBH | THURN-UND-TA XIS-STR. 22 | D-90411 NÜRNBERG | GERMANY | FON +49 (0) 911 51947- 0 | w w w.S plusS.de
7
Operating instructions
RYM
ASKON
®
600 - BACnet
RYM
ASKON
®
600 - Modbus
88
52
53
112
28.5
20.5
(CO2-Sensor)
14.5
(Standard)
TOUCHSCREEN
50 x 75
DIMENSIONAL DRAWING
Dimensional drawing
[mm]
WIRING
Connection diagram
Typ 610
(
Basic model)
WARNING:
Switch off the power supply before commencing the wiring work!
AI2 AI1 DI1
G0
B–
A+
Y2
Y3
Y1
G0
24V
G0
RYMASKON 610
0..10V DC Analogue Outputs
Y1
AO1 – default fan speed
Y2
AO2 – default heating stage 1
Y3
AO3 – default cooling stage 1
24V
24V AC/DC Supply
G0
GND
0-10V Analogue Inputs
AI1
Analogue Input 1 (RI optional)
AI2
Analogue Input 2 (RI optional)
DI1
Digital Input (potential-free)
Modbus / BACnet MS/TP
A+
RS485 A+
B–
RS485 B–