Operating instructions 

RYM

ASKON

®

    600 - BACnet 

RYM

ASKON

®

    600 - Modbus

ALARM INDICATOR  
CO2, HUMIDITY,  
TEMPERATURE

The controller provides 

two

 

alarm channels

 to show if set limit values were exceeded/undercut.  

Alarm sources

 are internal temperature, humidity or CO2 sensors (for units with RH/CO2 option).  

For example, you can set “Alarm 1” to the CO2 concentration and “Alarm 2” to room air humidity.  
The default alarm function for the alarm source is “None”, i.e., it is disabled. 

Every alarm has three levels: 

No alarm 

(without icon), 

amber alarm

   and

 red alarm

  .  

 

If an alarm is active, an amber or a red bell is shown in the small action circle on the display.  
The action circle consecutively shows all active measurements, i.e., the alarm is shown with its reading. 

The following parameters can be separately configured for every alarm channel:
• Alarm Source 
• Alarm Amber Threshold
• Alarm Red Threshold
• Alarm Hysteresis

Whether an alarm is triggered by exceeding or undercutting a limit value  
is automatically determined by the higher threshold of red or amber.  
The following descriptions illustrate this principle:

HIGH LIMIT ALARM

Amber 

Thershold

Range

0...5000

Range

0 = Default

Red 

Thershold

HIGH LIMIT ALARM

Alarm because of 

exceeding

 a limit value,  

if threshold 

Red higher than amber

 is set: 

Sensor value  

  threshold amber  →  no alarm (without icon) 

Sensor value  

  threshold 

amber

  →  

alarm

 indicated by amber bell 

Sensor value  

  threshold 

red

 

→  

alarm

 indicated by red bell 

Hysteresis prevents returning to a lower alarm level until  
the sensor value 

goes down

 to a threshold 

minus

 hysteresis.

LOW LIMIT ALARM

Amber 

Thershold

Range

0...5000

Range

0 = Default

Red 

Thershold

LOW LIMIT ALARM

Alarm because of 

undercutting

 a limit value  

if threshold 

Amber higher than red

 is set:

Sensor value  

  threshold 

red

 

→  

alarm

 indicated by red bell 

Sensor value  

  threshold 

amber

  →  

alarm

 indicated by amber bell 

Sensor value  

  threshold amber  →  no alarm (without icon)

Hysteresis prevents returning to a lower alarm level until  
the sensor value 

goes up

 to a threshold 

plus

 hysteresis.

Содержание Rymaskon 600

Страница 1: ...947 0 www SplusS de Operating instructions RYMASKON 600 BACnet RYMASKON 600 Modbus Room control unit with colour touch screen with BACnet or Modbus connection Controller for controlling and regulating...

Страница 2: ...g this unit close to other devices that do not comply with EMC directives may influence the functionality thereof This unit must not be used for monitoring purposes which serve the purpose of protecti...

Страница 3: ...ode is exited the unit performs a soft reset Alternatively the new settings can also be activated by switching the unit off and on again deactivate and reactivate supply voltage The configuration para...

Страница 4: ...ration of temperature fan light 1 zone and sun protection 2 zones via touch display 3 analogue outputs 0 10 V for controlling heating cooling valves and EC motor 2 analogue inputs 0 10 V for external...

Страница 5: ...ture fan light 1 zone and sun protection 2 zones directly via the analogue outputs or via the bus TECHNICAL DATA Basic model Device type room control unit with controller Functions temperature fan lig...

Страница 6: ...see number key above ACCESSORIES RYMASKON USB_CT Configuration Tool for quick transfer of the device configuration from the PC to all devices in the building 1901 51Z3 0002 000 Pos 1 4 Type name RYMA...

Страница 7: ...ng mm WIRING Connection diagram Typ 610 Basic model WARNING Switch off the power supply before commencing the wiring work AI2 AI1 DI1 G0 B A Y2 Y3 Y1 G0 24V G0 RYMASKON 610 0 10V DC Analogue Outputs Y...

Страница 8: ...an speed 1 RLY2 RO2 fan speed 2 RLY3 RO3 fan speed 3 RCOM Relay Common 24V 24V AC DC Supply G0 GND 0 10V DC Analogue Outputs Y2 AO2 default heating stage 1 Y3 AO3 default cooling stage 1 0 10V Analogu...

Страница 9: ...DO1 default heating PWM TR2 Triac2 DO2 default cooling PWM 0 10V Analogue Inputs AI1 Analogue Input 1 RI optional AI2 Analogue Input 2 RI optional DI1 Digital Input potential free Modbus BACnet MS TP...

Страница 10: ...ROL WITH MODULATING EC FAN Heating Cooling 0 10V DC 0 10V DC Heating Control 0 10V DC EC Fan Control 0 10V DC EC Fa Digital Input Night Override e g Door Window Switch External Sensor Fan Coil Unit RY...

Страница 11: ...backlighting standby If the display of the main screen is not touched for 30 sec the display will be dimmed to the configured standby value default 5 max 20 Use the settings to adjust the brightness...

Страница 12: ...CIRCLE CONTROL BAR HIGH LOW LIMIT CONTROL BRIGHTNESS DISPLAY Outside 10 5 C Humidity 45 RH MAIN SCREEN Fig 2 CONTROL BLINDS max 2 zones LIGHT ECO MODE active ALARM with bell icon configurable Page 30...

Страница 13: ...ssioning Fig 3a Temperature in C Fig 3b Temperature in F Room 22 7 C 18 3 C C F Room 72 8 F 65 0 F C F If the icon for switching between C F is enabled Settings Display Show Unit Swap Enabled the temp...

Страница 14: ...HDz Heating Deadzone and CDz Cooling Deadzone to asymmetrically set the dead zone left and right of the calculated setpoint calcSP In some cases it may be important for the cooling process to respond...

Страница 15: ...odes for inputs RI1 and RI2 the controller can be used for limit value control via High Limit Setpoint default 35 C and Low Limit Setpoint default 16 C This function is enabled via the parameter Limit...

Страница 16: ...tained If released the toggle icon Light remains active see chapter Light The current position of the blind is maintained in ECO mode If released the Blind toggle icon remains active ECO MODE Display...

Страница 17: ...sition of the blinds is maintained in OFF mode If released the Blind toggle icon remains active If the room temperature in OFF mode drops below the antifreeze setpoint antifreeze is enabled see diagra...

Страница 18: ...tput can be configured for Max VAV maximum volume flow In that case the relevant output Y1 Y2 Y3 takes on the maximum consumption capacity of the CO2 and of the cooling temperature control circuit Typ...

Страница 19: ...nfigurable boost time The boost time timer can be configured from 0 to 480 minutes 0 permanently enabled switch off boost using the display or the bus The remaining time is shown on the touch display...

Страница 20: ...ON WILL ROTATE AUTOMATIC CONTROL A AUTO CAN BE SELECTED VIA THE BUS OR ON THE UNIT MAIN SCREEN AUTO CONTROL CONTROLLED VIA THE BUS UNIT SWITCHES TO AUTO AS SOON AS A NEW SPEED IS SPECIFIED VIA THE BUS...

Страница 21: ...n speed Min Fan Level and Fan switch off delay Fan Off Delay work 1 Example Min Fan Level 20 Fan Off Delay 0 s This configuration lets the fan run at 20 while the control circuit is in the dead zone 2...

Страница 22: ...Configuration of Light mode Additionally you can configure a lights switch off delay Lights Delay Time When the light is switched off switch off delay regardless of the lights mode or the comfort ECO...

Страница 23: ...ement types can be configured as follows Blind mode increments 2 positions On Off 5 positions 4 increments 11 positions 10 increments Infinite 1 increments The positions are distributed equally from 0...

Страница 24: ...alue is not displayed Bus NTC10K The input is available for temperature recording using the connected NTC10K sensor via the bus no control function The temperature value is not displayed Bus AI option...

Страница 25: ...losed to open the operating mode changes only after the timer configured in the parameter Digital Input Delay has counted down Changeover You can use the digital input for priority switching from heat...

Страница 26: ...d CO2 see chapter Fan speed control and CO2 control circuit Max Fan Max Fan CO2 The 0 10 V output is linked to the maximum capacity of the control circuits for CO2 and blower see chapter CO2 control c...

Страница 27: ...ay outputs to control the fans the operating mode of the analogue output Y1 must be set to Fan default NOTE Types 620 650 have been designed for a maximum nominal resistive load of 0 5 A Types 630 660...

Страница 28: ...erate a 3 speed fan using the three relays RLY1 2 3 see chapter Relay outputs blower control In both cases ensure to set the operating mode of the Y1 analogue output to EC fan to control the fan see c...

Страница 29: ...RED TEMPERATURE 100 0 6 PORT CONTROL MODE DEMAND 6 WAY VALVE CONTROL SIGNAL Y1 Y2 Y3 MAX FLOW MIN FLOW 2V SQUENCE 1 SQUENCE 2 10V H E A T I N G S T A G E 1 C O O L I N G S T A G E 1 nSP Nominal Setpoi...

Страница 30: ...d Alarm Red Threshold Alarm Hysteresis Whether an alarm is triggered by exceeding or undercutting a limit value is automatically determined by the higher threshold of red or amber The following descri...

Страница 31: ...configuration Settings System Language The operator of the room control unit can also be authorised to change the user interface language To this end a toggle icon can be released in the settings as...

Страница 32: ...icon to enable cleaning mode 30 s timer Lock icon to enable and detect locking mode display lock multiple access levels are available ECO icon to enable ECO mode extended dead zone disable it via the...

Страница 33: ...e can be defined to activate deactivate the locking state Lock Code default 0000 no PIN required NOTE The display lock is also retained if the unit is switched off and back on again The following conf...

Страница 34: ...y entering the PIN code the Parameter Groups are displayed The info icon is located at the bottom of the display Tap the Info icon to display detailled status information about the current state of co...

Страница 35: ...s NOTE Changed communication parameters are activated when setting mode is exited the unit performs a soft reset Alternatively the new settings can also be activated by switching the unit off and on a...

Страница 36: ...ximum admissible downwards adjustment of the target temperature 20 0 0 C F default 3 0 PB Proportional band of the temperature control circuit 1 0 50 0 C F default 4 0 IA Integral reset time of the te...

Страница 37: ...it value control 0 0 5 0 default 0 0 disabled Changeover Low Lower Limit in changeover mode where the unit automatically switches into cooling mode cold water supply see chapter Changeover 0 0 95 0 C...

Страница 38: ...Contact Alarm 7 Network 8 Close for Boost 9 Open for Boost Digital Input Delay Delay time of the digital inputs when switching from active to inactive 0 28800s default 0s RI1 mode Operating mode of in...

Страница 39: ...ure control relay output OPEN CLOSE NOTE Y2 is not available for RYMASKON types 640 and 660 These types require the Thermic 1 2 Mode to be configured Y3 Assignment of output capacity from control circ...

Страница 40: ...and releases the control on the main screen 0 Disabled 1 Htg Stage 1 default 2 Htg Stages 1 2 3 Clg Stage 1 4 Clg Stages 1 2 5 Humidification 6 De Humidification 7 CO2 8 Fan 9 Aux Loop RYMASKON 600 S...

Страница 41: ...teps 3 10 steps 4 Infinite Blind 1 Configuration Releases the graphical display of the movement type of blind 2 and the relevant variables for manual control 0 Level translatory movement UP DOWN 1 Til...

Страница 42: ...Comfort ECO ALARMS Parameter name Description Range Alarm 1 Source Source for alarm indicator alarm 1 0 CO2 sensor 1 Room Temperature 2 Humidity 3 None Default Alarm 1 Amber Threshold Switching point...

Страница 43: ...o Input Display lock icon displayed active only blinds adjustment possible 0 Disabled Default 1 On Off Only 2 Adjust Only 3 No Input Lock Code PIN for enabling disabling the display lock 0000 no PIN r...

Страница 44: ...l statements and data herein represent our best knowledge at date of publica tion They are only meant to inform about our products and their application potential but do not imply any warranty as to c...

Отзывы: