Operating instructions
RYM
ASKON
®
600 - BACnet
RYM
ASKON
®
600 - Modbus
MODES FOR
ANALOGUE OUTPUTS
The controller has
three
analogue outputs (0...10 V DC) and they are typically linked to the control circuit outputs.
The following configuration options are available:
•
Bus
Operated as 0...10 V output variable for the bus
•
Heating stage 1 (Htg Stage 1)
The 0...10 V output is linked to heating stage 1 (default:
Y2
)
•
Heating stage 2 (Htg Stage 2)
The 0...10 V output is linked to heating stage 2
• Cooling stage 1 (Clg Stage 1)
The 0...10 V output is linked to cooling stage 1 (default:
Y3
)
• Cooling stage 2 (Clg Stage 2)
The 0...10 V output is linked to cooling stage 2
• Fan (Modulating Fan)
The 0...10 V output is linked to the fan control circuit output (default:
Y1
)
•
CO2 control (CO2)
The 0...10 V output is linked to the CO2 control circuit outputs
(see chapter “CO2 control circuit”)
•
Max. VAV (Max. Clg
/
CO2)
The 0...10 V output is linked to the maximum capacity of the control circuits for cooling stage 1 and CO2
(see chapter “Fan speed control” and “CO2 control circuit”)
•
Max. Fan (Max. Fan
/
CO2)
The 0...10 V output is linked to the maximum capacity of the control circuits for CO2 and blower
(see chapter “CO2 control circuit”)
•
Humidification
The 0...10 V output is linked to the control circuit output for humidification
(see chapter “Humidity control circuit”)
•
De-humidification
The 0...10 V output is linked to the control circuit output for de-humidification
(see chapter “Humidity control circuit”)
•
Light
0...10 V linked to lighting stage
•
Blind 1 Level
0...10 V linked to blind 1 position
•
Blind 1 Tilt
0...10 V linked to the blind 1 slats’ angle of inclination
•
Blind 2 Level
0...10 V linked to blind 2 position
•
Blind 2 Tilt
0...10 V linked to blind 2 slats’ angle of inclination
•
Amber
/
red alarm
0...10 V is at 50 % if the amber or the red alarm is active
•
Red alarm (Red)
0...10 V is at 100 % if the red alarm is active
•
Heating stage 1 static (Htg Stage1 Stat)
(see chapter “Relay output/ON-OFF”)
•
Cooling stage 1 static (Clg Stage1 Stat)
(see chapter “Relay output/ON-OFF”)
• Fan static (Fan Stat)
(see chapter “Relay output/ON-OFF”)
• AUX control circuit (Aux. Loop)
(see chapter “AUX control circuit”)
•
6-way valve (6-Port)
(see chapter “6-way valve control”)
•
6-way valve inverse (6-Port Reverse)
(see chapter “6-way valve control”, inverse mode).