OPTIONAL PROGRAMS

NOTE: The Digital Gateway has one programmable

output (output 7), two programmable inputs
(inputs 24 and 26) and various other pro-
gram options built in. A description of  each
available program follows. See SETTING
THE PROGRAM OPTIONS on page 15 for
programming instructions.

PROGRAM 1, OUTPUT 7

This output can tell you if the door is not closed, fully
open or about to close. When output 7 is turned on
115 vac will be available at terminal 7. This power can
be used to turn on a 115 vac relay which can indicate
where the door is or what it is about to do. The relay
can operate warning lights, horns or signal an energy
management system. Only one of the three options
available in Program 1 can be selected at a time.

Door Not Closed, P1 = LSC

Output 7 will be on when the door is not closed. (Not
on the "Close" limit switch). The output will be off when
the door is fully closed. (On the "Close" limit switch).
This is the factory default setting. It tells you the door
is not closed.

Door Open, P1 = LSO

Output 7 will be on when the door is fully open. (On
the "Open" limit switch). The output will be off when
the door is below the open position. (Off of the "Open"
limit switch). It tells you the door is fully open.

Delay to Close, P1 = dtC

When the door is signaled to close, output 7 will turn
on, the Delay to Close timer (dtC) will start, but output
6, which closes the door will not be on. When the
Delay to Close timer times out, output 6 will activate
and the door will close. Output 7 will remain on until
the door is completely closed. Maximum time is 15
seconds. This option tells you the door is about to
close.

PROGRAM 2, INPUT 24

This input can be used to place the Digital Gateway
into an inactive condition, operate the door manually or
automatically or open the door to a height below fully
open. Only one of the Program 2 options can be
selected at a time.

LOC Condition, P2 = LOC

When input 24 is on and the door is fully closed the
Digital Gateway will go into an inactive condition. No
inputs will be able to activate the door. The message
LOC will be on the display. Once the connection is
removed from the input, the system will be ready for
normal operation. This is the factory default Program 2
setting and can be used to "lock out" the door.

MAN-AUTO Selector Switch, P2 = SSA

If this option is selected, a manual-automatic two
position selector switch can be connected to input 24.
When the switch is in the MAN position  (there is no
connection at terminal 24) the A/A and Auto Close
delay timers are disabled. The Auto and Loop inputs
are inactive when the door is closed, but will reverse
the door if it is closing or hold it open when it is fully
open.

When the switch is in the AUTO position (there is a
connection at input 24) the A/A Close Delay timer will
turn on and all inputs will operate normally.

This option allows you to operate the door manually or
automatically.

MAN-AUTO Selector Switch with Open and Close
Inactive in Auto, P2 = SSb

This option operates the same as the MAN-AUTO
option described in MAN-AUTO Selector Switch, P2 =
SSA, except in the Auto position the Open and Close
inputs are inactive.

Passage Entry—Timed, P2 = Pet

When this option is used and the door is activated to
open with input 24, it will open for a predetermined
time. This allows you to open the door part way with an
activator connected to terminal 24 while other activa-
tors connected to other inputs will open the door
completely. A 20 foot door could be opened 8–10 feet
for small loads and 20 feet for large loads.

When input 24 is activated while the door is fully
closed the door will open and the Passage timer (PEt)
will begin counting down. When the Passage timer
reaches zero the door will stop. Activating this input
again will close the door. If the A/A Close Delay timer
is on when the door is opened with input 24, the door
will open until the Passage timer reaches zero. Then
the A/A Close Delay timer will time out and close the
door.

OPTIONAL PROGRAMS

Содержание DG1215

Страница 1: ... Revision April 15 1998 0 215 007 Rytec Corporation Digital Gateway Installation Owners Manual Model DG1215 ...

Страница 2: ......

Страница 3: ...TO THE DIGITAL GATEWAY 4 LIMIT SWITCHES TERMINALS 8 AND 9 4 Open LSO 4 Close LSC 4 PB1 PUSHBUTTON TERMINAL 11 4 ALTERNATE ACTION INPUTS A A MOMENTARY CONTACT ACTIVATORS TERMINAL 12 4 AUTO INPUTS MAINTAINED CONTACT ACTIVATORS TERMINAL 14 4 PHOTOEYE TERMINAL 15 5 REVERSING EDGE TERMINAL 17 5 OLR OVERLOAD RELAY TERMINAL 18 5 OPEN TERMINAL 20 5 CLOSE TERMINAL 21 5 STOP RESET TERMINAL 23 5 PROGRAM 2 TE...

Страница 4: ...CONNECTIONS 9 OP 0 OPEN TIME EXCEEDED 9 CL 0 CLOSE TIME EXCEEDED 9 AJAr BREAKAWAY KILL SWITCH 10 OLr OVERLOAD RELAY 10 EdGE REVERSING EDGE 10 NON ALARM CONDITIONS HELLO SAFE START UP 11 EdGE REVERSING EDGE TRIPPED 11 LOC IDLE STATE 11 POWER 12 OUTPUTS 12 REPLACEMENT 12 TROUBLESHOOTING 12 OPTIONAL PROGRAMS 13 PROGRAM 1 OUTPUT 7 13 Door Not Closed 13 Door Open 13 Delay to Close 13 PROGRAM 2 INPUT 24...

Страница 5: ...Position 14 PROGRAM 3 INPUT 26 14 Photoeye AC 14 Passage Limit Switch LSP 14 PROGRAM 4 PROGRAMMABLE OPTIONS 14 Close Jog 14 Open Jog 14 Reverse Delay 14 Loop Call Delay 14 PROGRAM 5 REVERSE INPUT LOGIC 14 PROGRAM 6 14 SETTING THE PROGRAM OPTIONS 15 REPLACING MODELS DG1000 AND DG1100 WITH DG1215 16 PAGE ...

Страница 6: ...This page intentionally left blank ...

Страница 7: ...onal injury if the procedure is not performed as described CAUTION is used to indicate the potential for damage to the product or property dam age if the procedure is not followed as de scribed IMPORTANT IMPORTANT is also used to re lay information CRITICAL to the successful completion of the pro cedure NOTE NOTE is used to provide additional infor mation to aid in the performance of the pro cedur...

Страница 8: ...re 1 for an overview of the Digital Gateway controls INTRODUCTION HELLO OPEN Backup Timer Digital Display Shows Cycles Timer Settings Alarm Conditions and Door Setting CLOSE Backup Timer UP Arrow Display Message Explanation A A Close Delay Timer Auto Close Delay Timer DOWN Arrow Input Connection Information Status LEDs Light is ON When Remote Contact Has Been Activated A0500030 OPEN Jog Button CLO...

Страница 9: ...ll operate while the Digital Gateway is in the AJAr or EdGE alarm condition See Figure 1 CLOSE JOG This pushbutton jogs the door closed It is not operational when the door is being controlled by any activator The close jog button will operate while the Digital Gateway is in the AJAr or EdGE alarm condition See Figure 1 UP ARROW DOWN ARROW In the normal operating mode these pushbuttons are used to ...

Страница 10: ...utton while the door is in the full open position will close the door The PB1 input can be converted to automatic closing Refer to the section on setting the timers The PB1 input works the same as the A A input described in the following ALTERNATE ACTION INPUTS A A MOMENTARY CONTACT ACTIVATORS TERMINAL 12 N O CONTACT A momentary connection while the door is closed closing or stopped between limits...

Страница 11: ...LED will blink To reset the system Re establish the connection then push the Open Jog Reset button or the Stop input See ALARM CONDITIONS on page 9 for more information OLR OVERLOAD RELAY TERMINAL 18 N O CONTACT When the overload relay in the control box detects a motor malfunction it will trip and turn off the motor contactors It will also send a signal to the Digital Gateway by closing the conta...

Страница 12: ...e detector will close This maintained connection will open the door if the door is closed closing or stopped between limits The door will remain open as long as the connection is present When the connection is removed the Auto Close delay timer will count down and close the door The Auto Close delay timer dEL will reset if another maintained connection is made while the timer is timing out If you ...

Страница 13: ...displayed as OP plus time CLOSE BACKUP TIMER This is the backup timer for the closing of the door It functions the same as the open backup timer When the time has been exceeded the display message CL 0 and the LSO LED will blink until the system has been reset This timer should be set 1 2 seconds longer than it takes the door to close Settings and messages for this timer will be displayed as CL pl...

Страница 14: ...kup Timer Push to Set the Timer A0500029 Figure 6 START UP PROCEDURES 1 Install the door following the procedures outlined in the door installation manual 2 Make all the necessary electrical connections Follow the electrical schematic shipped in each door s control box The schematics shown in this manual are for informational purposes only See INPUTS TO THE DIGITAL GATEWAY on page 4 for a descript...

Страница 15: ...EXCEEDED This alarm indicates that the open backup timer has timed out before the door has fully opened and that the door has not operated in the time set on the backup timer The display message OP 0 and the LSO LED will blink Check the door for proper operation and reset the Digital Gateway See Figure 8 OP 0 A0500029 Figure 8 CL 0 CLOSE TIME EXCEEDED This alarm indicates that the close backup tim...

Страница 16: ...Digital Gateway See Figure 11 OLr A0500029 Figure 11 EdGE REVERSING EDGE This alarm indicates that the reversing edge connec tion input 17 is missing The Digital Gateway moni tors the connection every time the door is fully open If the connection is missing for 2 seconds or more the door will remain open the display message EdGE and the RE input LED will blink Reconnect the input and reset the Dig...

Страница 17: ... displayed if the door comes down on something activating the reversing edge The door will reverse to the open position To reset the system and close the door use the PB1 A A or Close input To reset the system and leave the door open use the Open Jog Reset button or the Stop input See Figure 14 EdGE A0500029 Figure 14 LOC IDLE STATE This message will be displayed when input 24 is activated the doo...

Страница 18: ... 16 Power Outputs A0500029 Figure 16 REPLACEMENT The fused disconnect must be in the OFF position and properly locked and tagged before performing the following procedure If the Digital Gateway ever requires replacement 1 Turn off the power to the door 2 Remove the plug in terminal blocks from the left side of the Digital Gateway 3 Remove the existing Digital Gateway from the control box by removi...

Страница 19: ... LOC When input 24 is on and the door is fully closed the Digital Gateway will go into an inactive condition No inputs will be able to activate the door The message LOC will be on the display Once the connection is removed from the input the system will be ready for normal operation This is the factory default Program 2 setting and can be used to lock out the door MAN AUTO Selector Switch P2 SSA I...

Страница 20: ...nstant pressure jog operation The door will only close while the input is activated Open Jog OPJ On OPJ OFF This option converts the Open Input input 20 to constant pressure jog operation The door will only open while the input is activated Reverse Delay rdt 00 The Digital Gateway is programmed to immediately reverse the door if an activator or safety input is operated while the door is closing Th...

Страница 21: ...0 s as shown in Figure 19 To continue the pro gramming mode you will have to enter the three digit security code Contact the Rytec Customer Support Department at 414 677 9046 for the code 000 A0500029 Figure 19 2 The first left digit will blink Press the UP or DOWN arrow key to raise or lower the value of the first digit After the first digit is set press the Select button to move to the next digi...

Страница 22: ... and the timer setting Use the UP and DOWN arrow keys to set the timers Figure 22 shows the Delay to Close timer set to 0 seconds Use the Set button to return to the Main Program menu A0500029 dtc 00 Figure 22 8 When all options have been selected press the Open and Close Backup Timer buttons to leave the program mode The Digital Gateway is then ready for operation REPLACING MODELS DG1000 AND DG11...

Страница 23: ...g Screws Mounting Screws Plug In Terminals Figure 23 REPLACING MODELS DG1000 AND DG1100 WITH MODEL DG1215 5 Install the replacement Digital Gateway with the four screws removed in step 4 6 Reconnect the plug in terminal blocks making sure the numbers on the terminal blocks corre spond with the terminal numbers on the replace ment Digital Gateway If required connect the loop wires to the new three ...

Страница 24: ...18 NOTES ...

Страница 25: ...19 NOTES ...

Страница 26: ...20 NOTES ...

Отзывы: