14
Passage Entry—Position, P2 = PEP
When this option is turned on PROGRAM 3, INPUT
26—Passage Limit Switch, LSP will also be turned on.
These two options allow you to open the door partially
using an activator connected into input 24 and another
limit switch (Passage Limit LSP) connected to input
26. A 20 foot door could be opened 8 feet for small
loads and 20 feet for large loads. The Passage Limit
would be set at 8 feet. Using the activator connected
to input 24 would open the door to the Passage Limit.
Using the other activators would open the door com-
pletely.
When input 24 is activated while the door is fully
closed it will open until it reaches the Passage limit
switch which will activate input 26. When input 24 is
activated again the door will close. If the A/A Close
Delay timer is used the door will open until it reaches
the Passage limit switch, then the A/A Close Delay
timer will time out and close the door. If the input is
activated while the door is closing the door will open
until it reaches the OPEN or Passage limit switch,
depending on which limit switch is tripped first.
PROGRAM 3, INPUT 26
This program option will not appear in the Program
Menu. These options are set through factory defaults
or by other program options.
Photoeye AC
This input will operate the same as the photoeye input
described in PHOTOEYE—TERMINAL 15 (N.C.
CONTACT) on page 5, except it would be used for AC
photoeyes. This is the factory default setting.
Passage Limit Switch, LSP
This option is turned on when the Passage Entry—
Position option is turned on. The Passage Limit switch
is connected to this input. When the door reaches the
Passage position after it is opened by input 24, this
input will be activated and the door will stop.
PROGRAM 4, PROGRAMMABLE OPTIONS
This program section allows you to change the Open
and Close inputs to constant pressure/jog, set a
reverse delay timer and/or a loop call delay. More than
one of these options can be on at the same time.
Close Jog, CLJ = On/CLJ = OFF
This option converts the Close Input (input 21) to
constant pressure/jog operation. The door will only
close while the input is activated.
Open Jog, OPJ = On/OPJ = OFF
This option converts the Open Input (input 20) to
constant pressure/jog operation. The door will only
open while the input is activated.
Reverse Delay, rdt = 00
The Digital Gateway is programmed to immediately
reverse the door if an activator or safety input is
operated while the door is closing. This option can be
used to delay the reversal of the door. If the A/A, Auto
or Open input is activated while the door is closing the
reversal will be delayed by the time set on the Reverse
Delay timer. The door will stop, the Reverse Delay
timer (rdt) will time out and the door will then open.
Reversals due to the photoeye or reversing edge
inputs will not be delayed.
The maximum setting is 15 seconds. The factory
default setting is 0 which disables the timer.
Loop Call Delay, LPt = 00
This option will delay the opening of the door when it is
opened by the Loop input. This can be used for cross
traffic situations.Traffic crossing in front of the door will
not remain on the loop long enough to open the door
but traffic approaching the door will activate the door.
When the Loop input is activated while the door is fully
closed the Loop timer will count down and then open
the door. If the Loop input returns to the normal
unactivated state while the timer is counting down the
door will not open and the system will return to the
normal state.
If the Loop input is activated while the door is closing
the door will immediately reverse to the fully open
position.
The maximum setting is 15 seconds. The factory
default setting is 0 seconds which disables the timer.
PROGRAM 5, REVERSE INPUT LOGIC
This option can be used to reverse the required logic
for some of the inputs. The required contact arrange-
ment can be changed from normally closed (N.C.) to
normally open (N.O.). The inputs that can be changed
are Open Limit (LSO - #8), Close Limit (LSC - #9),
Photoeye—DC (Pdc - #15), Reversing Edge (rE -
#17), Stop (StP- #23), Program 3 (PG3 - #26) and
Breakaway Limit (LSb - #27).
PROGRAM 6
This program option is set for factory use. It requires
an additional three digit security code. If you find
yourself in program 6 press the Set button to return to
the main menu.