Current value table, protocol addresses 14 (outputs)
Current value table, protocol addresses 24 (error numbers)
Bit 0
Reserved
Bit 1
Reserved
Bit 2
1 = Cooling requirement
Bit 3
1 = Rotor motor
Bit 4
Reserved
Bit 5
1 = Heating valve open
Bit 6
1 = Heating valve closed
Bit 7
1 = Heating pump on
Bit 8
1 = Unit defective
Bit 9
1 = Damper closed
Bit 10
1 = Damper open
Bit 11
1 = Cooling valve open
Bit 12
1 = Cooling valve closed
Bit 13
1 = Enable frequency converter
Bit 14
Reserved
Bit 15
Reserved
Value
0
No error
1
Supply-air temperature sensor defective
2
Room-air temperature sensor defective
3
Outlet-air temperature sensor defective
4 Exhaust-air temperature sensor defective
5
Outdoor-air temperature sensor defective
6
Damper position
7
Frost protection triggered
8
Safety thermostat triggered
9
Thermal switch for ventilator triggered
10
Error fan
11 Reserved
12
Not enabled
13
Cooling plant defective
14
Fire detector
15 Reserved
16 Reserved
17
Supply-air temperature too low
18
Supply-air temperature too hot
19 Reserved
20
Heat exchanger
13. Dismantling and disposal
Dismantle the unit as follows:
•
Risk of injury if dismantled under hazardous voltage!
»
If you do not switch off the voltage before starting to dismantle the unit you may injure your-
self and damage the product or parts of the installation.
→
Make sure that the relevant parts of the installation have been disconnected from the volt-
age supply.
12. Expansion and reconfiguration
The unit must not be reconfigured.
The warranty for
ruck
fans only applies for the configuration delivered.