11.4. Parameter table
Register
address
Protocol
address
Parameter name
Value range
Data type Authority
40001
0
Reserved
integer
R/W
40002
1
Minimum target temperature
100 - 200 corresponds 10.0 - 20.0 °C
integer
R/W
40003
2
Maximum target temperature
200 - 350 corresponds 20.0 - 35.0 °C
integer
R/W
40004
3
External error input
0 = Automatic start
5 = Start after acknowledgement
integer
R/W
40005
4
I - component of heating con-
troller
5 - 20
5 = 0.5 min
20 = 2 min
integer
R/W
40006
5
P - component of heating
controller
5 - 20
integer
R/W
40007
6
Temperature-correction sensor -50 - +50 corresponds to -5.0 -+5.0 °C
integer
R/W
40008
7
Modbus address
1 - 247
integer
R/W
40009
8
Modbus baud rate
0 = 2400 ; 1 = 4800 ; 2 = 9600 ; 3 = 14400 ; 4= 19200
Baud
integer
R/W
40010
9
Fan calibration supply air
800 - 1200
integer
R/W
40011
10
Fan calibration extract air
800 - 1200
integer
R/W
40012
11
Reserved
integer
R/W
40013
12
Reserved
integer
R/W
40014
13
Units
0 = Air volume control
1 = Pressure control
2 = Supply air pressure control Extract air volume control
integer
R/W
40015
14
External sensor type
0 = Constant air volume 1 = CO2 sensor
2 = VOC sensor 3 = EXT.CTRL.
integer
R/W
40016
15
Minimum ventilation supply air
See Table below or 50 - 500 Pa
integer
R/W
40017
16
Minimum ventilation extract air
See Table below or 50 - 500 Pa
integer
R/W
40018
17
Basic ventilation supply air
See Table below or 50 - 500 Pa
integer
R/W
40019
18
Basic ventilation extract air
See Table below or 50 - 500 Pa
integer
R/W
40020
19
Intermittent ventilation supply air
See Table below
integer
R/W
40021
20
external set-point (CO2, VOC)
CO2/VOC Range of values 600 - 1500PPM
integer
R/W
40022
21
Type of regulation
0 = Room temperature
1 = Supply-air temperature
2 = Outlet-air temperature
integer
R/W
40023
22
Function (heating – cooling coil) 0 = Heating (Water)
1 = Cooling (Water)
2 = Heating and cooling (Water)
3 = Heating condenser and cooling DX-coil
integer
R/W
40024
23
Min. value when analogue input
0V external sensor
0 - 500 for CO2 and VOC sensor
integer
R/W
40025
24
Max. value when analogue input
10V external sensor
0 - 5000 for CO2 and VOC sensor
integer
R/W
40026
25
Sensor contamination filter 1
0 - 500 Pa Pressure loss
integer
R/W
40027
26
Sensor contamination filter 2
0 - 500 Pa Pressure loss
integer
R/W
40028
27
Calibrate filter
1 = Calibrate filter
integer
R/W
40029
28
Intermittent ventilation extract air See Table below
integer
R/W
40030
29
rotor
0 = 1000 1 = 1700 2 = 2800 3 = 4200 4 = 7600
integer
R/W
40031
30
Follow-up time motion detector 60 - 3600 sec
integer
R/W
40032
31
Target temperature
Minimum - maximum target temperature in 1/10 degree integer
R/W
40033
32
Ventilation change-over
1 = Minimum ventilation 2 = Basic ventilation
3 = Intermittent ventilation
integer
R/W
40034
33
Status and control word
See Table below
integer
R/W
40035
34
Reserved
integer
R/W
40036
35
Save parameters
12439 Value change after saving under 0
integer
R/W