Control unit outputs
Display of the assigned outputs on the control unit.
Control unit inputs
Display of the assigned inputs on the control unit.
Hours of operation
The current number of hours for which the unit has been in constant operation.
•
Value x 10 in hours.
Filter change counter
Number of filter changes made. The value rises automatically whenever a filter has been correctly
changed.
The individual outputs can be queried with the
selection tools „▲“ and „▼“
The selection is made from right to left.
Description:
0 = no relay connected
1 = relay connected
The individual inputs can be queried with the
selection tools „▲“ and „▼“
The selection is made from right to left.
Description:
1 = true
0 = false
Position: Consequence:
Description:
1
unimplemented
UNUSED
2
unimplemented
UNUSED
3
1 = on
ENABLE COLDNESS
4
1 = on
ROTOR MOTOR
5
unimplemented
UNUSED
6
1 = opening
HEAT.VALVE OPEN
7
1 = closing
HEAT.VALVE CLOSE
8
1 = on
CIRCULATOR PUMP
9
1 = error
FAULT RELAIS
10
1 =
closing
AIR FLAP CLOSE
11
1 = opening
AIR FLAP OPEN
12
1 = opening
COOL.VALVE OPEN
13
1 = closing
COOL.VALVE CLOSE
14
1 = on
ENABLE FRQ. CONV.
15
unimplemented
UNUSED
16
unimplemented
UNUSED
Position: Consequence: Description:
1
UNIT ENABLE
2
1 = OK
FRQ. CONVERT.FAULT
3
1 = OK
MOTOR PROTECTION
4
1 = OK
FROST PROTECTION
5
MOTION DETECTOR
6
1 = OK
FIRE PROTECTION
7
ROTATION CONTROL
8
1 = OK
ROTOR PROTECTION
9
unimplemented
UNUSED
10
unimplemented
UNUSED
11
unimplemented
UNUSED
12
unimplemented
UNUSED
13
unimplemented
UNUSED
14
unimplemented
UNUSED
15
unimplemented
UNUSED
16
unimplemented
UNUSED